SYSTEM AND METHOD OF ADVANCED DIGITAL ECONOMIZATION
20220155743 · 2022-05-19
Assignee
Inventors
- Justin James Sipe (Federal Way, WA, US)
- Daniel E. Miller (Renton, WA, US)
- Gerald B. Scott (Seattle, WA, US)
- Kenneth Hellewell (Seattle, WA, US)
Cpc classification
F24F11/65
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/77
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2110/10
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/62
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Y02B30/54
GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
F24F11/38
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/0001
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2011/0002
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2140/00
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/30
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2011/0006
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/64
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/46
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2110/12
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
International classification
F24F11/00
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/30
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Abstract
Systems and methods include a controller that compares an indoor temperature with a dead-band range having a heating setpoint and a cooling setpoint and that operates an HVAC system in an economizer mode to cool an indoor building space by introducing outside air to the indoor building space, prior to a call for cooling being received, in response to the indoor temperature being within the dead-band range and increasing.
Claims
1. A method comprising: receiving, with a controller, an indoor temperature from an indoor space sensor located in an indoor building space, the controller being in communication with an HVAC system that is configured to provide heating in response to a call for heating from a temperature controller and to provide cooling in response to a call for cooling from the temperature controller; comparing, with the controller, the indoor temperature with a dead-band range having a heating setpoint and a cooling setpoint, the cooling setpoint being greater than the heating setpoint, the call for heating being generated by the temperature controller in response to the indoor temperature being less than the heating setpoint and the call for cooling being generated by the temperature controller in response to the indoor temperature being greater than the cooling setpoint; and operating, with the controller, the HVAC system in an economizer mode to cool the indoor building space by introducing outside air to the indoor building space, prior to the call for cooling being received, in response to the indoor temperature being within the dead-band range and increasing.
2. The method of claim 1 wherein operating, with the controller, the HVAC system in the economizer mode includes modulating an outdoor air damper between a fully closed and a fully opened position to maintain a supply air setpoint.
3. A system comprising: a controller in communication with an HVAC system that is configured to provide heating to an indoor space in response to a call for heating from a temperature controller and to provide cooling to the indoor space in response to a call for cooling from the temperature controller, the controller being configured to: receive an indoor temperature from an indoor space sensor located in the indoor building space; compare the indoor temperature with a dead-band range having a heating setpoint and a cooling setpoint, the cooling setpoint being greater than the heating setpoint, the call for heating being generated by the temperature controller in response to the indoor temperature being less than the heating setpoint and the call for cooling being generated by the temperature controller in response to the indoor temperature being greater than the cooling setpoint; and operate the HVAC system in an economizer mode to cool the indoor building space by introducing outside air to the indoor building space, prior to the call for cooling being received, in response to the indoor temperature being within the dead-band range and increasing.
4. The system of claim 3 wherein the controller is further configured to operate the HVAC system in the economizer mode by modulating an outdoor air damper between a fully closed and a fully opened position to maintain a supply air setpoint.
5. A system comprising: an HVAC assembly configured to provide heating, cooling, and ventilation functions to an indoor building space, the HVAC assembly including a variable speed fan; an economizer configured to provide an economization function to the indoor building space, the economizer including at least one damper to outside air; an inside air sensor configured to sense an indoor temperature of the indoor building space; a controller configured to: receive the indoor temperature sensed by the inside air sensor; compare the indoor temperature with a dead-band range having a heating setpoint and a cooling setpoint, the cooling setpoint being greater than the heating setpoint; in response to determining that the indoor temperature is greater than the heating setpoint, less than the cooling setpoint, and increasing: (i) operate the economizer in a cooling mode to introduce outside air to the indoor building space prior to a call for cooling being received when the sensed indoor temperature becomes greater than the cooling setpoint and (ii) maintain a target airflow through the economizer by increasing an opening of the at least one damper and decreasing a speed of the variable speed fan.
6. A system comprising: an HVAC assembly configured to provide heating, cooling, and ventilation functions to the indoor building space, the HVAC assembly including a variable speed fan; a controller configured to receive sensor data, receive input data from the HVAC assembly that indicates an operating mode, and send data to the HVAC assembly to operate and monitor the heating, cooling, and ventilation functions; an economizer configured to provide an economization function, wherein the economizer is interconnected to the ventilation functions of the HVAC assembly and includes at least one damper to outside air; and an outside air sensor configured to sense conditions of the outside air and transmit data that represents the sensed conditions to the controller, wherein: the damper is configured to operate between a fully closed position and a fully open position in response to receiving a signal from the controller, the controller is configured to determine a target airflow through the economizer and predictively operate the economizer in a predictive cooling mode based on the outside air conditions sensed by the outside air sensor, and operating the economizer in the predictive cooling mode includes maintaining the target airflow through the economizer by (i) increasing the opening of the damper and (ii) operating the variable speed fan at a low speed.
7. The system of claim 6 wherein the controller is configured to predictively operate the economizer in the predictive cooling mode prior to receiving input data from the HVAC assembly that indicates a cooling mode.
8. The system of claim 6 wherein the controller is configured to verify efficiency of the economizer.
Description
BRIEF DESCRIPTION OF THE DRAWINGS
[0013] Like reference numerals are used to designate like parts throughout the several views of the drawings, wherein:
[0014]
[0015]
[0016]
[0017]
[0018]
[0019]
[0020]
[0021]
[0022]
[0023]
[0024]
DETAILED DESCRIPTION OF THE INVENTION
[0025] Referring to
[0026] According to one aspect of the invention, the system utilizes an advanced digital economizer (ADE) that consists of a computerized processing unit, environmental sensors, and an interface to an HVAC system. The ADE includes the ability to connect to the HVAC conditioning control points, fan command and fan speed, and an economizer actuator. It has the ability to provide standard low voltage thermostat type control signals to HVAC equipment and modulating resistive or voltage signal to the economizer actuator. The ADE can be used with either new or existing equipment. The ADE can be implemented in a commercially available controller (like an Easy IO 32), a PLC (like an ABB AC500), or embedded directly on a programmable chip (like a MicroChip PIC24). At its core is the ability to store instructions, accept commands, retain setpoints, and react to sensor inputs.
[0027] The ADE can use temperature and humidity sensors to monitor environmental conditions. The sensor will provide a varying electrical signal based upon the conditions. For example, the temperature sensor could be a 10K NTC thermistor that changes the resistive value based on temperature changes. For humidity measurements, the sensor could be a 0-10 VDC sensor, where the voltage output changes based on changes in the humidity. It is also required for the ADE to receive indication of the space conditions. This can come either from a variable resistive or voltage signal, but it can also be transmitted to the controller through on/off or digital inputs.
[0028] The prior art for demand control ventilation provides energy savings when the outside air temperature is extreme. The reduction in outside air results in energy savings. The outside air that is brought into the space has to be treated to reach proper occupant comfort level. This is demonstrated in
[0029] During mild conditions when the outside air could be used for free cooling. DCV would result in an energy penalty. DCV provides a reduction in outside air. As demonstrated in the chart in
[0030] Referring to
[0031] Referring now to
[0032] Referring also to
[0033] When the ADE is equipped with a space sensor, the space conditions will be used to determine when the controller will use the advanced ventilation control [
[0034] Referring now to
[0035] The ADE will support multiple configurations. Changes will be either configured on the controller through dip switches, potentiometers, or through a user interface which can be a local LCD with push buttons, a hand held tool, or a computer interface. The configuration will allow the user to change the application, configure sensors, adjust setpoints, and initiate calibration.
[0036] The ADE will control the quantity of outside air that is being supplied to the space by controlling the economizer [1.2], commonly expressed as the economizer position. When the economizer position is indicated in this document, it is referencing the percentage of the outside air in relation to the total air handling capacity of the unit. For example, a 20% economizer position means 20% of the air delivered by the air handler comes through the outside air dampers. Therefore, 80% of the air is being recirculated from the space as return air. If the HVAC system has a constant volume fan, the outside air flow will be adjusted by making changes to the economizer actuator position. If it is a variable volume system, the ADE will control the volume of outside air by controlling both the fan speed and the economizer actuator position. The ADE will modulate the outputs to find the corresponding values that can produce the required air mixture using the lowest amount of energy to achieve the desired outcome. By default, the ADE will first increase the damper position before increasing the fan speed, which results in higher energy use.
[0037] Referring to
[0038] The ADE can accept signals from the existing temperature controller [1.9] or new temperature controller [2.5]. The most common interface will be though digital inputs. The existing control system will send an on/off command that will be monitored by the ADE. It will be able to accept Stage 1 Heat, Stage 2 Heat, Stage 1 Cool, Stage 2 Cool, and reversing valve commands. The existing control will be routed to the ADE, and the ADE will connect to the HVAC system control terminals. Alternately the ADE can become the temperature controller and replace the existing controls. When the ADE is the temperature controller it will store occupied and unoccupied heating and cooling setpoints [6.15] and it will monitor the space temperature. It will provide the control signals for the fan [1.5], and it will enable the fan to run in the occupied mode. When the space temperature is less than the heat setpoint, heating [1.6] will be enabled. When the space temperature is greater than the cooling setpoint, the unit will go into the cooling mode. When the ADE is in the cooling mode the economizer [1.2] or mechanical cooling [1.7] can be used to meet the demands of the space. The heating or cooling output will increase based on the deviation from setpoint and how long the deviation has existed. It will use proportion, integral, and derivative (PID) control loop and a sequencer [6.16] to stage the conditioning functions. In either connection when the space is occupied and there is no call for heating or cooling, the system is determined to be in the ventilation mode.
[0039] Another embodiment of the ADE involves an HVAC system with modulating heating and cooling valves. In this application, the ADE will operate the heating and cooling functions with a varying analog output signal.
[0040] Any variation of the ADE can also be configured for demand control ventilation (DCV). DCV is a common practice that is supported by the ASHRAE 62.1 standard. It is used to determine the proper ventilation rate for a building based on occupancy. The most common way to monitor the occupants in a space is by using a CO2 sensor [3.1]. The CO2 sensor provides a voltage output that increase as the CO2 levels in the space increase. The DCV control sequence will be overridden whenever the controller initiates the Advanced Ventilation mode as described below. When DCV is engaged, the minimum ventilation settings will be reset based on the occupancy levels. The minimum and maximum ventilation rates will be set based on ASHRAE 62.1 guidelines, commonly the minimum ventilation rate will be set to 5-10% outside air volume and 20-40% for the maximum rate. As the CO2 in the space increases, the economizer output will increase to maintain the appropriate ventilation rate.
[0041] An alternate embodiment would allow ADE to use a timing method to determine when the advanced ventilation mode can be utilized [7.5]. The ADE would consider the space satisfied and to have a cooling disposition when a period of time, such as 45 minutes, has elapsed following the termination of the last heating call [2.7]. The ADE would then modulate the economizer [2.2] to maintain a supply air [2.4] temperature setpoint (such as 60° F.) to prevent overcooling. If no heating calls have happened for the selected time period following the beginning of occupancy, the ADE would then enter the advanced economizer mode and modulate the economizer [2.2] to achieve a supply air temperature such as 65° F. The occupied period is assumed to have occurred when the supply fan command [2.6] transitions from off to on.
[0042] When one or more valid environmental sensor is connected to the ADE, the ADE may automatically select the application mode that is used to determine the dead-band range. [
[0043] For example: if the space sensor is valid [7.2], the dead-band range will be the occupied heating and cooling setpoints [7.7]. If the sensor goes invalid, the ADE will transition to the return air sensor [7.3], and the return air high economizer lockout and balance point setting is used to establish the dead-band range [7.8].
[0044] If the ADE is controlling based on the outside air sensor and if either of the supply outside air sensors returns an invalid reading, the ADE would be disabled from operating [7.6].
[0045] Referring now to
[0046] The illustrated embodiments are only examples of the present invention and, therefore, are non-limitive. It is to be understood that many changes in the particular structure, materials, and features of the invention may be made without departing from the spirit and scope of the invention. Therefore, it is the Applicant's intention that its patent rights not be limited by the particular embodiments illustrated and described herein, but rather by the following claims interpreted according to accepted doctrines of claim interpretation, including the Doctrine of Equivalents and Reversal of Parts.