Direct Room Economizer
20220082272 ยท 2022-03-17
Inventors
Cpc classification
F24F2221/52
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2011/0002
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2140/40
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F1/56
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2110/22
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2130/10
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2011/0006
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F13/12
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F2007/0025
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/46
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/58
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/0001
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
International classification
F24F1/56
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F24F11/46
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Abstract
A device and a method to provide direct room air cooling. The device is a duct-less economizer that runs independent of existing HVAC systems. The device has its own thermostat setting and is capable of providing significant insulation values when closed. In addition, the method by which the device determines the availability of cool air is improved. This is achieved by using internet weather data, to read outdoor heat indexes, instead of primarily relying on local sensors.
Claims
1. A dynamic venting device comprising: a frame; an adjustable insulating gate located within the frame; an electric motor that can adjust the position of the gate; and a control board.
2. The device in claim 1, wherein the frame is structured in such a way that it can be mounted directly in a wall or window, separate from existing HVAC, in order to push or pull air between rooms, or the outdoors.
3. The device in claim 1, wherein the insulating gate can seal well enough to provide sufficient insulating and air blockage properties, that it can deter heat index change through the wall or window.
4. The device in claim 1, wherein the insulating gate can be opened in such a manner as to allow air to pass through the wall or window when signalled by the control board.
5. The device in claim 1, wherein the frame or insulating gate may contain a bug screen, air filter, or one or more fans to facilitate the movement of sufficient volumes clean air through the window or wall to change the heat index in a target room.
6. The device in claim 1, wherein the control board may be configured by any number of buttons, touchscreens or external wireless technologies such as Wi-Fi and Bluetooth.
7. The device in claim 1, wherein the outer frame may have temperature and humidity sensors positioned on the front and back side of the frame, in order to determine the relative heat indexes on both sides of the gate.
8. The device in claim 1, wherein the frame may also be affixed inside a mounting harness, comprising an awning component that may in turn be installed in a wall or window, in order to prevent rain from entering the gate when it is open.
9. A room heat index control method, consisting of: a software program operating on an economizer control board that may wirelessly communicate with the internet; intermittent reading of weather data from the internet, or a local network, or from sensors attached to the economizer; and the ability for the economizer control board to adjust the air flow through the economizer gate.
10. The method of claim 9, wherein the software may attempt to intermittently use internet weather data to most accurately determine the outdoor heat index, or optionally use values read from local sensors, when the network is unavailable, or, an averaged value of both data sources, when both are available.
11. The method of claim 9, wherein the software may attempt to intermittently use internet weather data to determine if the economizer may pre-cool the target room below the current thermostat settings, in the early morning, when the weather forecast indicates that a warm day is possible.
12. The method of claim 9, wherein the software may retain user settings in control board memory such as the thermostat, differential heat index thresholds to open the gate, whether pre-cooling should be enabled, the number of degrees below regular thermostat cooling that will be tolerated when pre-cooling, and the temperature value at which is considered a hot day.
13. The method of claim 9, wherein the software will activate the control board to open the gate and circulate available cool air into the room when the room requires cooling.
Description
BRIEF DESCRIPTION OF DRAWINGS
[0011]
[0012]
[0013]
[0014]
[0015]
[0016]
[0017]
[0018]
[0019]
[0020]
DETAILED DESCRIPTION
[0021] The standard economizer usually consists of a metal chamber attached to the ducts of an HVAC system of a building, near the air conditioning unit. The control board of the air conditioning unit can therefore be used to work in conjunction with the dampers found inside the economizer to control the air flow. This design works, partly because ducts provide implied insulation, since stagnant air has an observable R-value, even if the outer housing of such a device is a poor insulator.
[0022] The concept of having an economizer directly installed in a specific room, without the use of ducts, therefore poses a problem with regards to energy loss, while the device is in a non-circulating air state. It therefore needs to be designed in such a manner as to better insulate over a shorter distance.
[0023] In addition, because a direct room economizer would typically need to be installed in the warmest parts of a building, it is likely that, unlike the standard economizer, that it has less variability in terms of placement. This could mean that the device is in direct sun, or, has no awning coverage to prevent rain from entering the unit. The device therefore needs consideration when dealing with these problems.
[0024]
[0025] In the event there is no protection from rain, the economizer would need to be placed into a harness (4) that has an awning component that prevents rain from entering the building when air the gate is open.
[0026]
[0027]
[0028]
[0029] The total width of the device should be such that it can fit between standard wall studs. This embodiment is 14.5 inches wide, which fits between a standard wall-stud spacing of 16 inches. When no harness is present, it is presumed that the structure of the building provides sufficient protection from rain above the installation point. Installation of the direct room economizer would also typically require spray foam insulation around the frame, in the cavity of the wall, to prevent any energy losses, when the device is not cooling.
[0030] In extreme cold climates, such a device may also require an insulating cover to be mounted over the entire front face, closing seams around the perimeter of the installation. Furthermore, the device may need to make an audio notification, when extreme hot or cold weather is detected; telling the user that they need to keep the device closed and sealed in such a manner. Unplugging the device may be required when the season dictates no energy saving is possible.
[0031]
[0032]
[0033] In
[0034]
[0035]
[0036] Because sensors exposed to direct sunlight, or, housed in devices that are exposed to direct sunlight can read as much as 10C above the actual surrounding air temperature, it is preferred to use wireless measurements that are not biased in such a manner. This is especially important for a device that has limited options for placement in a warm room. It is highly likely that the device will be placed in direct sunlight, in fact. Therefore, the preferred method when assessing whether the gate should be opened, is to use a wireless connection to the internet, in order to retrieve local weather information. However, the backup sensors may be used, as an alternative data source, should the internet not be accessible for any reason. These sensors can be reasonably reliable when the sun sets.
[0037] Furthermore, with internet access, the device then becomes capable of retrieving weather forecasts, and determining, in advance, if it is going to be a warm day. As such, we can permit a pre-cool option for these days. When pre-cooling, the device would pull cool air into the building, even below the regular thermostat settings, in the hours before the temperature is expected to rise above the regular thermostat setting. The amount of tolerance below thermostat, as well as the temperature at which we consider it a warm day, can be configured by the user. This process would further enhance the energy efficiency of the device, when enabled.
[0038]
[0039]
[0040] Another embodiment of a harness, not illustrated, would be one that has a width and height matched to slide into a wall mount air conditioner slot. With the economizer permanently attached at the face of the harness in such a manner, it could replace existing wall mount air conditioners on a seasonal or year-round basis.
[0041] If the harness is built with light-weight materials such as aluminum, the net weight of it, with an economizer built into it, may be light enough to allow us to also install it by resting it against a panel of polystyrene pressed up against the front surface of a window. The opening for the harness in the polystyrene panel would be on the lower edge, when installed this way. The front lips of the harness would then press against the panel, using the weight of the awning component to hold both the panel and the harness in places. Minimal other bracing would be needed in such an arrangement and it would allow for quicker installation and removal for season installation in windows.