Method and apparatus for staged startup of air-cooled low charged packaged ammonia refrigeration system
11156392 · 2021-10-26
Assignee
Inventors
- Jake William Denison (Germantown, MD, US)
- Donald Lee Hamilton (Westminster, MD, US)
- Samuel K Vineyard, II (Casey, IL, US)
Cpc classification
F25B43/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B39/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2400/13
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2600/2519
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B5/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B41/20
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2339/04
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2600/0271
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2400/0401
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B49/027
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2339/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B6/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B41/31
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2500/26
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B39/04
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
International classification
F25B41/40
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B41/20
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B41/31
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B39/04
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B43/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Abstract
An apparatus for staged startup of air-cooled low charged packaged ammonia refrigeration system includes motorized valves on condenser coil inlets, a main compressor discharge motorized valve, a bypass pressure regulator valve in the main compressor piping, and check valves on the condenser outlets. The condenser inlet motorized valves provide precise control of gas feed to the condensers, so pressure can build without collapsing oil pressure. The condenser outlet contains check valves to prevent liquid backflow during coil isolation. The compressor discharge line contains a motorized valve for regulating discharge pressure at start-up. The motorized valve in the compressor discharge piping includes a bypass with a pressure regulator for precise regulation at minimum discharge pressure. Once discharge pressure rises above the setpoint, the condenser inlet solenoid coils open one at a time. The discharge pressure regulating motorized valve simultaneously regulates the discharge pressure until the condenser maintains discharge pressure.
Claims
1. A method for start-up of an air-cooled ammonia refrigeration system having an evaporator, liquid/vapor separator, a compressor, an air-cooled condenser having a plurality of condenser coils, and a collection vessel without the need for a stand-alone oil pump to maintain oil pressure during start-up, said method comprising: starting refrigerant flow through said condenser coils one at a time; waiting to start refrigerant flow through each subsequent condenser coil until each prior started condenser coil is running at constant discharge and oil pressure; using a motorized valve in a discharge line from said compressor for control of gas flow out of said compressor; using a bypass pressure regulator valve in said discharge line from said compressor for additional control of gas flow out of said compressor; using motorized valves at an inlet of at least one condenser coil in said air-cooled condenser to control gas feed to said condenser coil; using check valves at an outlet of at least one condenser coil to prevent liquid backflow during coil isolation; monitoring gas pressure in said discharge line from said compressor and controlling the opening of said motorized valves based on said monitored gas pressure using a microcontroller or programmable logic controller.
Description
BRIEF DESCRIPTION OF THE DRAWINGS
(1)
(2)
(3)
(4)
DETAILED DESCRIPTION
(5)
(6) The system includes evaporators 2a and 2b, including evaporator coils 4a and 4b, respectively, condenser 8, compressor(s) 10, expansion devices 11a and 11b (which may be provided in the form of valves, metering orifices or other expansion devices), pump 16, liquid-vapor separation device 12, and economizer 14. According to one embodiment, liquid-vapor separation device 12 may be a recirculator vessel. According to other embodiments, liquid-vapor separation device 12 and economizer 14 may one or both provided in the form of single or dual phase cyclonic separators. The foregoing elements may be connected using standard refrigerant tubing in the manner shown in
(7) According to the embodiment shown in
(8)
Single Compressor Penthouse Improved Startup Configuration and Method
(9) Referring to the single compressor embodiment (
(10) A single condenser bundle is open to ensure proper surface is available during start-up. As the system begins increasing load, valves 101, 102 and 103 will begin to open. Once all valves are open, variable fan control takes over pressure control. The sequencing of the use of valves and fan operation can vary, based on system operation and design.
(11) Motorized valve 104 and ammonia pressure regulator valve 105 provide precise ammonia gas control during start-up of the system in low ambient conditions. During start-up, all motorized valves are closed and the pressure regulator provides compressor differential pressure control to ensure proper oil flow. The ammonia pressure regulator 105 provides low volume flow control. As the compressor begins to load, more ammonia gas flow is generated. Motorized valve 104 begins to open and control the discharge pressure, compressor differential pressure and oil flow.
(12) The next step during system start-up is to begin opening the condenser motorized valves 101, 102 and 103 and concomitant staging the startup of the condenser fans.
(13) Check valves 106, 107, 108 and 109 installed at the outlet to the condenser bundles are utilized to ensure liquid ammonia does not backflow into the condenser or other coil bundles during periods of downtime or normal operating periods.
(14) Each of valves 101, 102, 103 and 105 are activated by attached microcontrollers or PLC (programmable logic control). A central microcontroller or PLC monitors the status of each valve, as well as discharge pressure, and directs the action of the valves accordingly for sequential startup of the condenser coils while maintaining gas and oil pressure.
(15) Not all valves are required for a every ambient condition. In fact, above a certain ambient temperature, low ambient control may not be required. Therefore, valves can be installed and arranged to optimize operation at startup based on the ambient temperature.
Dual Compressor Penthouse Improved Startup Configuration and Method
(16) (Isolated Compressor Operation)
(17)
(18) Motorized valves 110, 111, 112 and 113 are installed on the inlet of the condenser coil bundles. The motorized valves can function as variable control valves or on/off valves.
(19) During startup, motorized valves 111 and 112 will be opened to a minimum position to allow ammonia gas flow to the condenser coil. As the system begins increasing load, valves 111 and 112 will open to 100% and valves 113 and 110 will begin opening. Once all valves are open, variable fan control takes over pressure control. The sequencing of the use of valves and fan operation can vary, based on system operation and design.
(20) Fine ammonia gas control during start-up of the system is provided by:
Compressor #1
(21) a. Valve #114 Motorized valve
(22) b. Valve #115 Pressure regulator
(23) c. Start-up requires all motorized valves are closed and the pressure regulator provides compressor differential pressure to ensure proper oil flow. During start-up, all motorized valves are closed and the pressure regulator provides compressor differential pressure control to ensure proper oil flow. The ammonia pressure regulator provides low volume flow control. As the compressor begins to load, more ammonia gas flow is generated. Motorized valve #114 begins to open and control the discharge pressure, compressor differential pressure and oil flow.
Compressor #2
(24) a. Valve #116 Motorized valve
(25) b. Valve #117 Pressure regulator
(26) c. Start-up requires all motorized valves are closed and the pressure regulator provides compressor differential pressure to ensure proper oil flow. During start-up, all motorized valves are closed and the pressure regulator provides compressor differential pressure control to ensure proper oil flow. The ammonia pressure regulator provides low volume flow control. As the compressor begins to load, more ammonia gas flow is generated. Motorized valve #116 begins to open and control the discharge pressure, compressor differential pressure and oil flow.
(27) The next stage is to begin opening the condenser motorized valves (110, 111, 112 and 113) and staging the condenser fans accordingly.
(28) Check valves (118, 119, 120 and 121) are utilized to ensure liquid ammonia does not backflow into the condenser or other coil bundles during periods of downtime or normal operating periods.
(29) As with the single compressor embodiment, each of valves 110-117 is activated by attached microcontrollers or PLC. A central microcontroller or PLC monitors the status of each valve, as well as discharge pressure, and directs the action of the valves accordingly for sequential startup of the condenser coils while maintaining gas and oil pressure. Not all valves are required for every ambient condition. In fact, above a certain ambient temperature, low ambient control may not be required. Therefore, valves can be installed and arranged to optimize operation at startup based on the ambient temperature.
(30) According to various embodiments, the evaporator is housed in the evaporator (penthouse) module, and the remaining components of the system shown in
(31) The combination of features as described herein provides a very low charge refrigeration system compared to the prior art. Specifically, the present invention is configured to require less than six pounds of ammonia per ton of refrigeration capacity. According to a preferred embodiment, the present invention can require less than four pounds of ammonia per ton of refrigeration. And according to most preferred embodiments, the present invention can operate efficiently with less than two pounds per ton of refrigeration capacity.
(32) While the present invention has been described primarily in the context of refrigeration systems in which ammonia is the refrigerant, it is contemplated that this invention will have equal application for refrigeration systems using other natural refrigerants, including carbon dioxide.
(33) The description of the invention is merely exemplary in nature and, thus, variations that do not depart from the concept of a packaged (one-or two-module integrated and compact system) low refrigerant charge (i.e., less than 10 lbs of refrigerant per ton of refrigeration capacity) refrigeration system are intended to be within the scope of the invention. Any variations from the specific embodiments described herein but which otherwise constitute a packaged, pumped liquid, recirculating refrigeration system with charges of 10 lbs or less of refrigerant per ton of refrigeration capacity should not be regarded as a departure from the spirit and scope of the invention set forth in the following claims.