Variable speed compressor protection system and method
10077774 ยท 2018-09-18
Assignee
Inventors
Cpc classification
F25B2500/08
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B39/12
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C28/08
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B31/006
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B2203/0209
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2600/021
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/21152
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C23/008
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/1931
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2500/28
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C18/0215
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B2203/0204
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Y10T137/0318
GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
F04B39/123
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2600/025
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C29/0085
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2270/19
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/21
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2240/803
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B39/06
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2210/26
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Y10T137/85986
GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
F25B2600/2513
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2240/403
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C28/24
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B49/005
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/21174
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Y02B30/70
GENERAL TAGGING OF NEW TECHNOLOGICAL DEVELOPMENTS; GENERAL TAGGING OF CROSS-SECTIONAL TECHNOLOGIES SPANNING OVER SEVERAL SECTIONS OF THE IPC; TECHNICAL SUBJECTS COVERED BY FORMER USPC CROSS-REFERENCE ART COLLECTIONS [XRACs] AND DIGESTS
F25B2500/19
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B49/06
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2240/81
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C2210/227
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C28/28
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/151
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/21151
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B49/022
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2700/21163
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
International classification
F04C28/08
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C28/24
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B49/06
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C18/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C23/00
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B39/12
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04B39/06
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F04C28/28
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B49/00
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B49/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Abstract
A system and method for a compressor includes a compressor connected to a condenser, a discharge line temperature sensor that outputs a discharge line temperature signal corresponding to a discharge line temperature of refrigerant leaving the compressor, and a control module connected to the discharge line temperature sensor. The control module determines a saturated condenser temperature, calculates a discharge superheat temperature based on the saturated condenser temperature and the discharge line temperature, and monitors a flood back condition of the compressor by comparing the discharge superheat temperature with a predetermined threshold. The control module increases a speed of the compressor when the discharge superheat temperature is less than or equal to the predetermined threshold.
Claims
1. A system comprising: a compressor connected to a condenser; a discharge line temperature sensor that outputs a discharge line temperature signal corresponding to a discharge line temperature of refrigerant leaving the compressor; a control module connected to the discharge line temperature sensor, said control module receiving compressor power data, determining a saturated condenser temperature as a function of the compressor power data and a speed of the compressor, calculating a discharge superheat temperature based on the saturated condenser temperature and the discharge line temperature, monitoring a flood back condition of the compressor by comparing the discharge superheat temperature with a predetermined threshold, and, when the discharge superheat temperature is less than or equal to the predetermined threshold, increasing the speed of the compressor.
2. The system of claim 1 wherein the predetermined threshold is thirty degrees Fahrenheit.
3. The system of claim 1 wherein the control module decreases an opening of an expansion valve associated with the compressor when the discharge superheat temperature is less than or equal to the predetermined threshold.
4. The system of claim 1 wherein the control module monitors a sudden flood back condition by determining whether the discharge superheat temperature decreases by a predetermined amount within a predetermined time period.
5. The system of claim 1 further comprising an evaporator connected to the compressor and the condenser, wherein the control module receives compressor power data, determines a saturated evaporator temperature as a function of the saturated condenser temperature, the discharge line temperature, and the speed of the compressor, and determines the saturated condenser temperature as a function of the compressor power data, the speed of the compressor, and the saturated evaporator temperature.
6. The system of claim 5 wherein the control module performs multiple iterations of determining the saturated condenser temperature and the saturated evaporator temperature to achieve convergence.
7. The system of claim 1 wherein the control module receives compressor power data and determines the saturated condenser temperature as a function of the compressor power data, the speed of the compressor, and the discharge line temperature.
Description
DRAWINGS
(1) The drawings described herein are for illustration purposes only and are not intended to limit the scope of the present disclosure in any way.
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
DETAILED DESCRIPTION
(19) The following description is merely exemplary in nature and is not intended to limit the present disclosure, application, or uses. It should be understood that throughout the drawings, corresponding reference numerals indicate like or corresponding parts and features.
(20) As used herein, the terms module, control module, and controller may refer to one or more of the following: An application specific integrated circuit (ASIC), an electronic circuit, a processor (shared, dedicated, or group) and memory that execute one or more software or firmware programs, a combinational logic circuit, or other suitable components that provide the described functionality. As used herein, computer readable medium may refer to any medium capable of storing data for a computer or module, including a processor. Computer-readable medium includes, but is not limited to, memory, RAM, ROM, PROM, EPROM, EEPROM, flash memory, CD-ROM, floppy disk, magnetic tape, other magnetic medium, optical medium, or any other device or medium capable of storing data for a computer.
(21) With reference to
(22) With reference to
(23) Inverter drive 22 includes solid state electronics to modulate the frequency of electrical power. Generally, inverter drive 22 converts the inputted electrical power from AC to DC, and then converts the electrical power from DC back to AC at a desired frequency. For example, inverter drive 22 may directly rectify electrical power with a full-wave rectifier bridge. Inverter driver 22 may then chop the electrical power using insulated gate bipolar transistors (IGBT's) or thyristors to achieve the desired frequency. Other suitable electronic components may be used to modulate the frequency of electrical power from power supply 18.
(24) Electric motor speed of compressor 10 is controlled by the frequency of electrical power received from inverter driver 22. For example, when compressor 10 is driven at sixty hertz electric power, compressor 10 may operate at full capacity operation. When compressor 10 is driven at thirty hertz electric power, compressor 10 may operate at half capacity operation.
(25) Piping from evaporator 16 to compressor 10 may be routed through enclosure 20 to cool the electronic components of inverter drive 22 within enclosure 20. Enclosure 20 may include a cold plate 15. Suction gas refrigerant may cool the cold plate prior to entering compressor 10 and thereby cool the electrical components of inverter drive 22. In this way, cold plate 15 may function as a heat exchanger between suction gas and inverter drive 22 such that heat from inverter drive 22 is transferred to suction gas prior to the suction gas entering compressor 10.
(26) As shown in
(27) A compressor floodback or overheat condition is undesirable and may cause damage to compressor 10 or other refrigeration system components. Suction super heat (SSH) and/or discharge super heat (DSH) may be correlated to a flood back or overheating condition of compressor 10 and may be monitored to detect and/or predict a flood back or overheating condition of compressor 10. DSH is the difference between the temperature of refrigerant vapor leaving the compressor, referred to as discharge line temperature (DLT) and the saturated condenser temperature (Tcond). Suction super heat (SSH) is the difference between the temperature of refrigerant vapor entering the compressor, referred to as suction line temperature (SLT) and saturated evaporator temperature (Tevap).
(28) SSH and DSH may be correlated as shown in
(29) A flood back condition may occur when SSH is approaching zero degrees or when DSH is approaching twenty to forty degrees Fahrenheit. For this reason, DSH may be used to detect the onset of a flood back condition and its severity. When SSH is at zero degrees, SSH may not indicate the severity of the flood back condition. As the floodback condition becomes more severe, SSH remains at around zero degrees. When SSH is at zero degrees, however, DSH may be between twenty and forty degrees Fahrenheit and may more accurately indicate the severity of a flood back condition. When DSH is in the range of thirty degrees Fahrenheit to eighty degrees Fahrenheit, compressor 10 may operate within a normal range. When DSH is below thirty degrees Fahrenheit, the onset of a flood back condition may occur. When DSH is below ten degrees Fahrenheit, a severe flood back condition may occur.
(30) With respect to overheating, when DSH is greater than eighty degrees Fahrenheit, the onset of an overheating condition may occur. When DSH is greater than one-hundred degrees Fahrenheit, a severe overheating condition may be present.
(31) In
(32) To determine DSH, DLT may be subtracted from Tcond. DLT may be sensed by a DLT sensor 28 that senses a temperature of refrigerant exiting compressor 10. As shown in
(33) In the alternative, a combination temperature/pressure sensor may be used. In such case, Tcond may be measured based on the pressure of refrigerant exiting compressor 10 as measured by the combination sensor. Moreover, in such case, DSH may be calculated based on DLT, as measured by the temperature portion of the sensor, and on Tcond, as measured by the pressure portion of the combination sensor.
(34) Tcond may be derived from other system parameters. Specifically, Tcond may be derived from compressor current and voltage (i.e., compressor power), compressor speed, and compressor map data associated with compressor 10. A method for deriving Tcond based on current, voltage and compressor map data for a fixed speed compressor is described in the commonly assigned application for Compressor Diagnostic and Protection System, U.S. application Ser. No. 11/059,646, Publication No. U.S. 2005/0235660. Compressor map data for a fixed speed compressor correlating compressor current and voltage to Tcond may be compressor specific and based on test data for a specific compressor type, model and capacity.
(35) In the case of a variable speed compressor, Tcond may also be a function of compressor speed, in addition to compressor power.
(36) A graphical correlation between compressor power in watts and compressor speed is shown in
(37) In this way, control module 25 may calculate Tcond based on compressor power data and compressor speed data. Control module 25 may calculate, monitor, or detect compressor power data during the calculations performed to convert electrical power from power supply 18 to electrical power at a desired frequency. In this way, compressor power and current data may be readily available to control module 25. In addition, control module 25 may calculate, monitor, or detect compressor speed based on the frequency of electrical power delivered to the electric motor of compressor 10. In this way, compressor speed data may also be readily available to control module 25. Based on compressor power and compressor speed, control module 25 may derive Tcond.
(38) After measuring or calculating Tcond, control module 25 may calculate DSH as the difference between Tcond and DLT, with DLT data being receiving from external DLT sensor 28 or internal DLT sensor 30.
(39) Control module 25 may monitor DSH to detect a flood back or overheat condition, based on the correlation between DSH and flood back and overheat conditions described above. Upon detection of a flood back or overheat condition, control module 25 may adjust compressor speed or adjust expansion valve 14 accordingly. Control module 25 may communicate with or control expansion valve 14. Alternatively, control module 25 may communicate with a system controller for refrigeration system 5 and may notify system controller of the flood back or overheat condition. System controller may then adjust expansion valve or compressor speed accordingly.
(40) DSH may be monitored to detect or predict a sudden flood back or overheat condition. A sudden reduction in DLT or DSH without significant accompanying change in Tcond may be indicative of a sudden flood back or overheat condition. For example, if DLT or DSH decreases by a predetermined temperature amount (e.g., fifty degrees Fahrenheit) within a predetermined time period (e.g., fifty seconds), a sudden flood back condition may exist. Such a condition may be caused by expansion valve 14 being stuck open. Likewise, a sudden increase in DLT or DSH with similar magnitude and without significant accompanying change in Tcond may be indicative of a sudden overheat condition due to expansion valve 14 being stuck closed. For example, if DLT or DSH increases by a predetermined temperature amount (e.g., fifty degrees Fahrenheit) within a predetermined time period (e.g., fifty seconds), a sudden overheat condition may exist.
(41) Control module 25 may monitor DSH and DLT to determine whether compressor 10 is operating within a predetermined operating envelope. As shown in
(42) In the event of a flood back condition, control module 25 may limit a compressor speed range. For example, when DSH is below thirty degrees Fahrenheit, compressor operation may be limited to the compressor's cooling capacity rating speed. For example, the cooling capacity rating speed may be 4500 RPM. When DSH is between thirty degrees Fahrenheit and sixty degrees Fahrenheit, compressor operating speed range may be expanded linearly to the full operating speed range. For example, compressor operating speed range may be between 1800 and 7000 RPM.
(43) The function correlating Tcond with compressor speed and power, may assume a predetermined or constant saturated Tevap. As shown in
(44) For additional accuracy, Tevap may be derived as a function of Tcond and DLT, as described in commonly assigned U.S. application Ser. No. 11/059,646, U.S. Publication No. 2005/0235660. For variable speed compressors, the correlation may also reflect compressor speed. In this way, Tevap may be derived as a function of Tcond, DLT and compressor speed.
(45) As shown in
(46) Tcond and Tevap may be calculated based on a single derivation.
(47) In addition, iterative calculations may be made based on the following equations:
Tcond=f(compressor power, compressor speed, Tevap) Equation 1:
Tevap=f(Tcond, DLT, compressor speed) Equation 2:
(48) Multiple iterations of these equations may be performed to achieve convergence. For example, three iterations may provide optimal convergence. As discussed above, more or less iteration, or no iterations, may be used.
(49) Tevap and Tcond may also be determined by using compressor map data, for different speeds, based on DLT and compressor power, based on the following equations:
Tevap=f(compressor power, compressor speed, DLT) Equation 3:
Tcond=f(compressor power, compressor speed, DLT) Equation 4:
(50) Once Tevap and Tcond are known, additional compressor performance parameters may be derived. For example, compressor capacity and compressor efficiency may be derived based on additional compressor performance map data for a specific compressor model and capacity. Such additional compressor map data may be derived from test data. For example, compressor mass flow or capacity, may be derived according to the following equation:
Tevap=f(compressor speed, Tcond, mass flow) Equation 5:
(51) Mass flow may be derived according to the following equation:
Mass Flow=m0+m1*Tevap+m2*Tcond+m3*RPM+m4*Tevap*Tcond+m5*Tevap*RPM+m6*Tcond*RPM+m7*Tevap^2+m8*Tcond^2+m9*RPM^2+m10*Tevap*Tcond*RPM+m11*Tevap^2*Tcond+m12*Tevap^2*RPM+m13*Tevap^3+m14*Tevap*Tcond^2+m15*Tcond^2*RPM+m16*Tcond^3+m17*Tevap*RPM^2+m18*Tcond*RPM^2+m19*RPM^3 Equation 6:
(52) where m0-m19 are compressor model and size specific, as published by compressor manufacturers.
(53) Compressor map data may be stored within a computer readable medium within control module 25 or accessible to control module 25.
(54) As shown in
(55) By monitoring the above operating parameters, control module 25 may insure that compressor 10 is operating within acceptable operating envelope limits that are preset by a particular compressor designer or manufacturer and may detect and predict certain undesirable operating conditions, such as compressor floodback and overheat conditions. Further, control module 25 may derive other useful data related to compressor efficiency, power consumption, etc.
(56) Where compressor 10 is driven by a suction cooled inverter drive 22, Tevap may be alternatively calculated. Because Tevap may be calculated from mass flow, Tcond, and compressor speed as discussed above, control module 25 may derive mass flow from a difference in temperature between suction gas entering cold plate 15 (Ts) and a temperature of a heat sink (Ti) located on or near inverter drive 22. Control module 25 may calculate delta T according to the following equation:
delta T=TsTi Equation 7:
(57) Ts and Ti may be measured by two temperature sensors 33 and 34 shown in
(58) Control module 25 may determine mass flow based on delta T and by determining the applied heat of inverter drive 22. As shown in
(59) Inverter heat may be derived based on inverter speed (i.e., compressor speed) and inverter efficiency as shown in
(60) With reference again to
(61) As shown by dotted line 141, Tcond and Tevap may be iteratively calculated to more accurately derive Tcond and Tevap. For example, optimal convergence may be achieved with three iterations. More or less iterations may also be used.
(62) As shown in
(63) As shown in
(64) In addition, similar to the calculation of DSH based on DLT described above, control module 25 may also calculate SSH. For example, compressor power, compressor speed, and compressor map data may be used to derive Tcond and Tevap may be derived from Tcond. Once Tevap is derived, SSH may be derived from SLT and Tevap and used as described above for monitoring various compressor operating parameters and protecting against flood back and overheat conditions.