Compact Low-power Cryo-Cooling Systems for Superconducting Elements
20220349628 · 2022-11-03
Assignee
Inventors
Cpc classification
F25B9/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B2309/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B9/10
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
International classification
F25B9/02
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
F25B9/10
MECHANICAL ENGINEERING; LIGHTING; HEATING; WEAPONS; BLASTING
Abstract
A compact, low power cryo-cooler for cryogenic systems capable of cooling gas to at least as low as 2.5 K. The cryo-cooler has a room temperature compressor followed by filtration. Within the cryostat, four counterflow heat exchangers precool the incoming high-pressure gas using the outflowing low-pressure gas. The three warmest heat exchangers are successively heat sunk to three stages of a pulse tube to absorb residual heat from the slight ineffectiveness of the heat exchangers. The pulse tube cold head also absorbs loads from instrumentation leads and radiation loads. The pulse tube stages operate at around 80 K, 25 K, and 10 K. The entire system—cryo-cooler, drive and control electronics, and detector instrumentation, fits in a standard electronics rack mount enclosure, and requires around 300 W or less of power.
Claims
1. A compact, low-power cryo-cooler system for cryogenic systems comprising: a cryo-cooler compressor for providing a flow of hot high-pressure gas and receiving a return flow of cool low-pressure gas; a series of counterflow heat exchangers configured to cool hotter incoming gas from the compressor with cooler gas returning to the compressor; a pulse tube cooler including a series of closed-cycle pulse tube cooling stages configured to interact with the counterflow heat exchangers to pre-cool the high-pressure gas to at least as low as 10 K; and a Joule-Thomson (JT) cooler configured to cool the pre-cooled gas to at least as low as 1.7 K, the JT cooler including an expansion capillary having a warm end and a cold end, wherein the warm and cold ends of the expansion capillary are physically separated enough to achieve sufficient thermal isolation between the warm and cold ends to achieve the 1.7K; wherein the cryo-cooler and associated drive and control electronics fit within a 7U electronics rack and the cooler and associated drive and control electronics require less than about 300 W of power.
2. The cryo-cooler of claim 1 wherein the cryo-cooler requires less than 250 W of power.
3. The cryo-cooler of claim 1 wherein the input pressure to the JT cooler is between 0.1 MPa and 0.2 MPa and the output pressure from the JT cooler is between 0.2 MPa and 1.3 kPa and wherein the output pressure is lower than the input pressure.
4. The cryo-cooler of claim 3 wherein the flow from the JT cooler is on the order of half a mg/sec.
5. The cryo-cooler of claim 1 having three pulse tube cooling stages, the three stages pre-cooling the gas to about 50-100K, 20-30K, and 6-10K in turn.
6. The cryo-cooler of claim 5 wherein the three cooling stages are implemented with a 3-stage linear compressor pulse tube operating at 35 Hz.
7. The cryo-cooler of claim 1 wherein the gas is 4He.
8. The cryo-cooler of claim 1 wherein the gas is 3He and the JT cooler is configured to cool the gas to around 1.25 K.
9. The cryo-cooler of claim 1 wherein the pulse tube stages have regenerators and pulse tube walls comprising stainless-steel tubing.
10. The cryo-cooler of claim 1 wherein the coldest pulse tube cooling stage utilizes erbium-nickel spheres.
11. The cryo-cooler of claim 1 wherein the counterflow heat exchangers are tube-in-tube.
12. The cryo-cooler of claim 1 wherein a JT expansion element within the JT cooler is comprises a 1 m-3 m long, 40 μm-60 μm inner-diameter stainless steel capillary
13. The cryo-cooler of claim 1 wherein the cold end of the expansion capillary is housed in copper block and the warm end of the expansion capillary is spaced apart from the copper block.
Description
BRIEF DESCRIPTION OF THE DRAWINGS
[0013]
[0014]
[0015]
[0016]
[0017]
[0018]
DETAILED DESCRIPTION OF THE INVENTION
[0019]
[0020] System 100 comprises a cryo-cooler compressor 102 providing high-pressure gas out 106 and low-pressure gas in 108 and includes a filter 104. Pulse tube cooler 130 includes an 80K stage 132, a 25K stage 134, and a 10K stage 136 housed within vacuum shell 150. Also within vacuum shell 150 are thermal busbar 142, heat exchangers 122, 124, 126, and 118, as well as counterflow heat exchangers 110, 112, 114, and 116. Counterflow heat exchanger 116 and heat exchanger 118 are part of JT stage 160, as is JT expansion capillary 120 (see
TABLE-US-00001 TABLE 1 JT Design Radiation Precooling Conduction Total Target Stage (mW) (mW) (mW) (mW) (mW) 80K 1000-2350 400 150 1550-2900 3000 25K 5-12 28 7 40-47 100 10K 0.2 2 1 3.2 5 2.0K 0 N/A 0.28 0.28 0.5
[0021] Estimated cooling loads on each of the cooler stages are presented in Table 1 along with the design goals. The cooling load on the JT stage 160 arises primarily from low thermal conductance bias/readout coaxial cables, since SNSPD's dissipate negligible power and photons are coupled in through optical fiber. Targeted cooling capacities included design margin at each stage. The 80 K stage 132 radiation load estimate has considerable uncertainty due to unknown ambient temperature since the cryo-cooler will generally be enclosed in an equipment rack-mounted box, and because of the uncertain surface emissivity of the radiation shield.
[0022] The WSi SNSPD detectors currently require cooling to 1.25 K for maximum quantum efficiency, but this temperature is difficult to achieve with a 4He JT refrigerator that utilizes a low power, compact compressor, and generally temperatures up to 2.5 K are acceptable. This 2.5 K minimum temperature is easily reachable by various embodiments of the present invention. Thus, this embodiment operates at a slightly higher minimum temperature of around 1.7 K/2.2 K. As an alternative, 3He does reach 1.25 K at the same pressure that 4He reaches 1.7 K, and can be used when the lower temperature is especially important.
[0023] Similarly, the 10 K for the precooling temperature for the JT stage 160 is a lower temperature than the thermodynamic optimum for this hybrid, but was chosen to reduce the high-pressure requirement for the JT loop, which in turn reduces stress on the JT compressor. This was done because the JT compressor is the largest risk to reliability. Final test results shown below show that the actual operating temperature of this stage was below 7.7 K. Again, for other applications, the operating conditions will be adjusted slightly.
[0024] The cooler is shown schematically in
[0025] The upper two-stage inertance tubes were dual diameters, whereas the third stage used only a single diameter because modeling indicated minimal improvement in performance with dual diameters. Regenerators used standard materials; the first stage used die-punched stainless steel screens with #150 mesh, 66 μm wire diameter in the warm side and #400 mesh, 25.4 μm wire diameter in the cold side. The second stage used #400 mesh, 25.4 μm wire diameter stainless steel screens in the warm side and #400 mesh, 25.4 μm wire diameter phosphor bronzes screens, flattened to produce 0.55 porosity, in the cold side.
[0026] The third stage used high heat capacity microspheres. In the previous embodiments, 100 um diameter 50-50 erbium-praseodymium (ErPr) alloy spheres were used. The present embodiment replaced the lower half of the regenerator with 100 μm diameter erbium-nickel (ErNi) spheres to improve cooling capacity below 10 K, and comparative tests results are presented below.
[0027] A critical mechanical design objective was geometries that minimize the effects of secondary flows within the pulse tube and regenerator, because these flows can seriously degrade performance. Most well known are turbulence/convection in the pulse tube and streaming in regenerators. Somewhat less appreciated are secondary flows in the displacer gap in Stirling coolers. A net circulation can flow through the displacer gap and return through the regenerator partially unregenerated and cause cooling loss unless there is sufficient lateral thermal conduction. Alternatively, because the displacer gap is dynamic, the local gap dimensions can vary during the operating cycle, causing local oscillating flow to not exactly reverse motion, again leading to unregenerated flow and cooling loss.
[0028] While it is well documented that, in large diameter regenerators, net circulation can lead to significant degradation in coolers, we were concerned that even in small diameter regenerators, some level of circulation can exist, causing measurable cooling loss. In multi-stage coolers, circulation can be generated in the regenerators near the junctions between stages, where the phasing of the flows between the upper stage regenerator, lower stage regenerator, and buffer tube will necessarily lead to circulation in the regenerators if the upper and lower stage regenerators are in-line with each other because flows entering the regenerator can come from either the adjacent regenerator or flow channel from the buffer tube. To mitigate this, some embodiments locate the second stage regenerator such that the warm entrance is in the connecting channel between the first stage regenerator and first stage pulse tube rather than directly in-line with the first stage regenerator.
[0029] Thus, the flow entering the cold end of the first stage regenerator always comes from the channel. This arrangement was not workable in this embodiment for the junction between the second stage and third stage regenerators because the second and third stage regenerator packing access was through an attachment flange for the third stage regenerator which was directly in line with the second stage regenerator. However, the small diameters of the second and third stages likely mitigated any effects of circulation.
[0030] For the JT system 160, the very low cooling capacity requirement allowed a design driven by ease of fabrication rather than by thermodynamics. The stage nominally operates between a high pressure of 200 kPa and a low pressure of 3.2 kPa, with a flow rate of 0.6 mg/s. The thermodynamic power required to recompress the gas is only a few watts, which is such a small fraction of the total power budget that a highly thermodynamically efficient design was not required.
[0031] All four counterflow heat exchangers 110, 112, 114, 116 are simple tube-in-tube designs, with high-pressure gas flowing in the narrow annular space between the two tubes and the low-pressure gas flowing through the inner tube This configuration simplifies fabrication, plus has a large internal surface area on the high-pressure return side to allow condensable contaminants to freeze out without plugging the flow passage.
[0032] The expansion impedance 120 was a 2 m long, 50 μm inner-diameter stainless steel capillary.
[0033] At the cold ends of the warmer three counterflow heat exchangers 110, 112, 114, a small heat exchanger consisting of fine mesh copper screen diffusion bonded to a copper body was used to heat sink the incoming gas to the pulse tube. The 1.7 K coldstage 116 also had a small copper screen mesh heat exchanger for thermal contact to the load (see
[0034] To mitigate particulate contamination, sintered stainless steel particulate filters 104 were inserted in the high-pressure line prior to entering the cryostat, at the end of the heat exchanger 132 at 80 K (not shown) and just upstream of the JT expansion impedance (not shown). In addition, a small capsule of activated charcoal (not shown) was placed in the high-pressure stream on the 80 K stage to adsorb any condensable contaminants.
[0035] To expedite cooldown of the JT coldstage from room temperature, a heat switch 140 consisting of a small bar that clamped down on a small copper tab attached to the JT coldhead was used. The clamp was heat-sunk to the pulse tube 10 K stage 136 and was actuated by pulling on a fine stainless steel wire attached to the bar (not shown). The far end of the wire was fed through a bellows feedthrough through the room temperature vacuum flange to allow actuation of the heat switch.
[0036] In the 2.2 K embodiment of
[0037] The JT compressor is a scroll compressor, selected because of the ability to achieve low suction pressures, compact size, and low per-unit cost. Because of the very low flow rates and low thermodynamic compression power, the JT loop did not require a high degree of optimization, so the counterflow heat exchangers were designed for ease of fabrication. They were modeled using a simple NTU analysis using temperature-averaged fluid properties, along with a separate calculation of thermal conduction down the heat exchanger tubes. There was considerable leeway in the design, allowing heat exchanger lengths to vary by a factor of two without significantly affecting performance. The main consideration was minimizing the demand on the JT compressor, so the system was designed for the lowest reasonable high-side pressure to minimize stresses on bearings and back-leakage through seals. Final flow and pressure requirements for the compressor were determined from test data.
[0038] Test results of the pulse tube:
[0039]
[0040]
[0041] These data were taken with no applied load to the upper two stages such that the upper stages ran colder than the data in Table 6, which resulted in higher 10 K cooling capacity.
[0042] Testing on the integrated JT-pulse tube coldhead was conducted open loop using a regulated compressed gas storage bottle as a supply and a vacuum pump vented to atmosphere on the return. The low side pressure was controlled by adjusting a valve in front of the vacuum pump.
[0043]
[0044] Test data described above show that the design point cooling powers for the pulse tube require a nominal 150 W of compressor power. We have tested a variety of commercial off-the-shelf power. Given conversion efficiencies of off-the-shelf power electronic modules for driving the compressor are generally better than 90%, the pulse tube will require a total power draw of about 165 W. The power draw by the compressor and drive electronics will be about 50 W. If the power for cooling fans and thermometry/diagnostic instrumentation is included, power requirements come in at under 300 W, usually about 250 W. In an embodiment using a smaller, commercially available, pulse tube compressor to reduce system weight, another 30 W-50 W of compressor power is required.
[0045] While the exemplary preferred embodiments of the present invention are described herein with particularity, those skilled in the art will appreciate various changes, additions, and applications other than those specifically mentioned, which are within the spirit of this invention. For example, for low heat load applications, the flow impedance can be increased, reducing the ass flow, which would reduce the power required for both the JT compressor and the pulse tube compressor. Conversely, there is substantial upside in the cooling power capability of the JT stage. The JT impedance can be reduced which would result in higher mass flow rates and higher cooling powers. The pulse tube has sufficient capacity to accommodate higher JT mass flow rates, so capacities approaching 5 mW are possible, although this will require development of a larger capacity JT compressor.
[0046] Lower temperatures using 4He are possible but require a combination of reworking the JT counterflow heat exchangers to reduce pressure drop, a JT compressor with lower suction pressure, and superfluid film creep mitigation. Direct substitution of 3He results in temperatures below 1 K.