TOPOLOGY AGNOSTIC DETECTION AND LOCATION OF FAULT IN DC MICROGRID USING LOCAL MEASUREMENTS
20230076181 · 2023-03-09
Inventors
Cpc classification
G01R31/085
PHYSICS
G01R19/2513
PHYSICS
H02H7/26
ELECTRICITY
H02H3/38
ELECTRICITY
International classification
Abstract
Systems and methods of determining fault location on a DC microgrid feeder need to be extremely fast to protect the circuit breaker and converter-source components. This disclosure develops a seminal theoretical foundation for fast fault location on a DC feeder that uses only single-ended local measurements in time domain. The theory provides a closed-form deterministic solution for fault location, making the resulting fault location method agnostic to system-topology and immune to fault resistance. The theory is developed with ideal DC voltage sources and is extended to practical converter-sources. The performance of the resulting method is demonstrated by simulating a DC feeder with converters connected at both ends, modeled in PSCAD (power systems computer-aided design).
Claims
1. A method of protecting a DC feeder electrical power network, the method including the steps of: providing one or more circuit breaker arrangements which on activation isolate electrical faults within the network; sampling voltage and current of the network at a relatively high sampling rate; determining the occurrence of and location of a fault in the network based on the sampled voltage and current; and activating one or more of the circuit breaker arrangements in response to determining the occurrence of a fault.
2. A method as in claim 1, wherein said determining includes calculating a current derivative.
3. A method as in claim 2, wherein said relatively high sampling rate is in a range between 100 KHz and 10 MHz.
4. A method as in claim 3, wherein said relatively high sampling rate is up to about 1 MHz.
5. A method as in claim 2, wherein said determining includes conducting three consecutive samplings of the voltage and current at up to about 1 MHz sampling rate.
6. A method as in claim 5, wherein said determining includes solving the equations:
7. A method as in claim 6, wherein solution for fault location x is determined by solving the equation:
8. A method as in claim 1, wherein the DC feeder electrical power network comprises at least one of a DC microgrid feeder and high voltage DC (HVDC) lines.
9. A method as in claim 1, wherein the circuit breaker arrangements are placed only on the positive pole of the DC feeder electrical power network.
10. A method of detecting and handling faults in a DC power transmission or distribution system network using only single-ended local measurements in time domain, using closed-form deterministic solution for fault location, such method comprising: providing one or more circuit breaker arrangements which on activation isolate electrical faults within the network; conducting three consecutive samplings of the network voltage and current at a relatively high sampling rate of up to about 1 MHz; determining the occurrence of a fault in the network based on calculating a current derivative from the sampled voltage and current; and activating one or more of the circuit breaker arrangements in response to determining the occurrence of a fault.
11. A method as in claim 10, further including determining the location of the determined fault in the network using a closed-form deterministic solution for fault location.
12. A method as in claim 11, wherein solution for fault location x is determined by solving the equation:
13. A method as in claim 10, wherein the DC power transmission or distribution system network includes at least one of a DC microgrid feeder and high voltage DC (HVDC) lines.
14. A fault protection system for protecting a DC feeder electrical power network, the system comprising: one or more circuit breaker arrangements which on activation isolate electrical faults within the network; and one or more processors programmed for: sampling voltage and current of the network at a relatively high sampling rate; determining the occurrence of and location of a fault in the network based on the sampled voltage and current; and activating one or more of the circuit breaker arrangements in response to determining the occurrence of a fault.
15. A fault protection system as in claim 14, wherein said one or more processors are further programmed for calculating a current derivative.
16. A fault protection system as in claim 15, wherein said relatively high sampling rate is in a range between 100 KHz and 10 MHz.
17. A fault protection system as in claim 15, wherein said one or more processors are further programmed for conducting three consecutive samplings of the voltage and current at up to about 1 MHz sampling rate.
18. A fault protection system as in claim 17, wherein one or more processors are further programmed for solving the equations:
19. A fault protection system as in claim 18, wherein said one or more processors are further programmed for solving for fault location x by solving the equation:
20. A fault protection system as in claim 14, wherein: the DC feeder electrical power network comprises at least one of a DC microgrid feeder and high voltage DC (HVDC) lines; and the circuit breaker arrangements are placed only on the positive pole of the DC feeder electrical power network.
Description
BRIEF DESCRIPTION OF THE DRAWINGS
[0026] A full and enabling disclosure of the presently disclosed subject matter, including the best mode thereof, directed to one of ordinary skill in the art, is set forth in the specification, which makes reference to the appended figures, in which:
[0027]
[0028]
[0029]
[0030]
[0031]
[0032]
[0033]
[0034]
[0035]
[0036]
[0037]
[0038]
[0039]
[0040] Table I is a chart of calculated distance x from Bus 1 to fault per a presently disclosed example in the subject specification;
[0041] Table II is a chart of parameters per a presently disclosed test system example in the subject specification;
[0042] Table III is a chart of performance of the presently disclosed method listing the sampling frequencies required to get the fault location error within ±1.5%;
[0043] Table IV is a chart of performance of the presently disclosed method with high resistance fault (Rf=2Ω) with increasing sampling frequency;
[0044] Table V is a chart of performance of the presently disclosed method with low resistance fault (Rf=0.01Ω) with decreasing sampling frequency;
[0045] Table VI is a chart of performance of the presently disclosed method with varying fault distance;
[0046] Table VII is a chart of performance of the presently disclosed method with varying DC link capacitor size;
[0047] Repeat use of reference characters in the present specification and drawings is intended to represent the same or analogous features or elements or steps of the presently disclosed subject matter.
DETAILED DESCRIPTION
[0048] Reference now will be made in detail to embodiments, one or more examples of which are illustrated in the drawings. Each example is provided by way of explanation of the embodiments, not limitation of the present disclosure. In fact, it will be apparent to those skilled in the art that various modifications and variations can be made to the embodiments without departing from the scope or spirit of the present disclosure. For instance, features illustrated or described as part of one embodiment can be used with another embodiment to yield a still further embodiment. Thus, it is intended that aspects of the present disclosure cover such modifications and variations.
Introduction
[0049] The rest of the disclosure includes Section II, theoretical proof of the proposed method with ideal DC voltage sources; Section III, which validates the theory with simulated data; Section IV, which shows how the method is applicable to a practical test feeder fed by converter-based sources; Section V, which shows how the method can be adapted for any value of fault resistance; Section VI, which includes sensitivity analysis of this method with respect to various parameters; and Section VII, which concludes the disclosure and describes future work.
II. Derivation of Theory for the Proposed Method with Ideal Sources
A. Fault Currents
[0050]
[0051] R.sub.1, L.sub.1=resistance and inductance, respectively, of line section from Bus 1 to fault.
[0052] R.sub.2, L.sub.2=resistance and inductance, respectively, of line section from Bus 2 to fault.
[0053] R, L=total resistance and inductance of line.
[0054] r, I=resistance and inductance per unit length of the line.
[0055] i.sub.1=Current from Bus 1 to fault.
[0056] i.sub.2=Current from Bus 2 to fault.
[0057]
(s.sup.2L.sub.1+s(R.sub.1+R.sub.f))I.sub.1+sR.sub.fI.sub.2=V.sub.1+sL.sub.1I.sub.0 (1)
sR.sub.fI.sub.1+(s.sup.2L.sub.2+s(R.sub.2+R.sub.f))I.sub.2=V.sub.2−sL.sub.2I.sub.0 (2)
[0058] If Eqs. 1 and 2 are solved for I.sub.1(s), I.sub.2(s) and subsequent inverse Laplace transforms are performed to get i.sub.1(t) and i.sub.2(t), the following expressions are obtained:
i.sup.1(t)=K.sub.1+K.sub.3*e.sup.−(λ.sup.
i.sub.2(t)=K′.sub.1+K′.sub.3*e.sup.−(λ.sup.
where
and K.sub.1, K.sub.3, K′.sub.1, K′.sub.3 are constants.
[0059] Stepwise derivation is provided in the supplementary material (Appendix A) submitted with this disclosure, and Appendix B calculates coefficients K.sub.1 and K.sub.3 for Section III using the relevant data from Eq. 13. Both Appendices A and B are part of this specification.
B. Fault Location Using Local Measurements
[0060] From Eqs. 3 and 4, the pre-fault current is
I.sub.0=K.sub.1+K.sub.3=−(K′.sub.1+K′.sub.3) (5)
[0061] Subtracting lo from Eq. 3, and adding the result to Eq. 4, the following expressions can be obtained:
i.sub.1(t)−I.sub.0=K.sub.1+K.sub.3*e.sup.−(λ.sup.
and,
i.sub.2(t)+I.sub.0=K′.sub.1+K′.sub.3*e.sup.−(λ.sup.
[0062] Dividing Eq. 7 by Eq. 6, Eq. 8 is obtained:
[0063] If the instantaneous fault voltage during the fault is v.sub.f(t), with corresponding source voltage at the sending end in
[0064] Using the expression of i.sub.2(t) from Eq. 8 in Eq. 9 and re-organizing terms, Eq. 10 can be obtained:
[0065] If v.sub.1, i.sub.1,
can be measured at two different times t.sub.1 and t.sub.2, Eq. 11 and Eq. 12 can be formed:
[0066] From Eqs. 11 and 12, the location of fault, x, can be expressed as:
[0067] Notice that Eq. 13 provides a closed-form solution for fault location that does not include the fault resistance term R.sub.f. Samples of voltage and current at time t.sub.1 and t.sub.2 can be measured, and if the sampling rate is high enough (1 MHz assumed in this disclosure), current derivative di.sub.1/dt can also be accurately measured. Thus, Eqs. 11 and 12 can be solved for fault location x and R.sub.f (m+1). Three consecutive readings are needed to solve the two equations, as two samples are needed to calculate di.sub.1/dt. This translates to a solution time of just 3 μs. Note that R.sub.f (m+1) is of no use, but x provides a closed-form solution for fault location in 3 μs. When the fault current will start to settle down, i.e.,
and i.sub.1(t.sub.1)≈i.sub.1(t.sub.2). In that case, both equations will have the same information, and the solutions will have the zero-determinant problem. So, it is important to use values during the transient state after a fault.
III. Validation of the Proposed Theory
[0068] To validate the theory developed in Section II, the circuit depicted in
[0069] Two faults are simulated at x.sup.(1)=80 m and x.sup.(2)=40 m distance from Bus 1. The fault inception time was set at t.sub.0=0.1 s for both cases. Currents from Bus 1 to fault (iBus1.sub.sim) for both cases are plotted in
[0070] For x.sup.(1)=80 m case, L.sub.1.sup.(1)=20 μH; L.sub.2.sup.(1)=5 μH; R.sub.1.sup.(1)=109.6 mΩ; and R.sub.2.sup.(1)=27.4 mΩ. So, L.sub.p.sup.(1)=L.sub.1.sup.(1)∥L.sub.2.sup.(1)=4 μH;
[0071] To get the expression of current in form of Eq. 3, values of coefficients K.sub.1.sup.(1) and K.sub.3.sup.(1) are needed. A detailed calculation of the coefficients is provided in the supplementary material (Appendix B). From the calculated values, current i.sub.1.sup.(1)(t) is
i.sub.1.sup.(1)(t)=2524.2843−2487.6497e.sup.−7980*t
However, since the fault in the circuit was simulated at t.sub.0=0.1 s, i.sub.1.sup.(1)(t) will be:
i.sub.1.sup.(1)(t)=2524.2843−2487.6497e.sup.−7980*(t−0.1) (14)
[0072] The calculated current using Eq. 14 is plotted in
[0073] To validate the method for fault location, measurements of three consecutive samples at three instances during the transient period after the fault initiation were made, and the fault distance was calculated using Eqs. 11 and 12 for each set of samples. In each case, the current derivative at a specific time-instant (say, t.sub.2) was calculated using measurement at that time instant and the previous measurement, i.e.,
[0074] Table I shows measured and calculated values at all three instances, for faults created at 80 m and 40 m from Bus 1. The calculated distance in each case is very close to the actual distance. The other variable being solved through Eqs. 11 and 12 is R.sub.f(m+1), which is of no interest to fault location. This result validates the closed-form deterministic theoretical formulation developed in Section II-B. So, it can be concluded that fault distance can be calculated, even in the presence of fault resistance, using local measurements only (in 3 μs), using the closed-form deterministic solution developed in Section II-B. This is claimed to be a seminal contribution of this work.
IV. Performance of the Method with Non-Ideal Sources
[0075] When a fault occurs on a feeder-section in a DC microgrid, the current contributions from the DC link capacitors associated with converters dominate the fault current first.sup.[4],[5]. As capacitors resist rapid change in voltage, for a short period of time after fault, the capacitor will act like a constant voltage DC source. Thus, measurements from this initial period can be used to determine the fault location modeled by Eqs. 11 and 12. This section describes the converter models, and fault detection and location on a feeder fed by converters.
A. LV DC Feeder Description
[0076]
[0077] The DC-DC boost converter model is taken from published literature .sup.[28]. Converter parameters are chosen using typical values for a 100-kW converter and verified through a number of resources.sup.[11], [23], [29], [30]. It is assumed that the converter has an ideal DC voltage source at its low voltage side, representing a PV panel or a battery. This is justified since the method is implemented in microseconds, and the input voltage can be assumed to be constant during that time. This is also justified since the inductor at the input side of the converter (L.sub.cnv) shown in
B. Currents Under Normal Loading and Fault Conditions in Converter Interfaced Feeders
[0078]
[0079] A fault was simulated in the DC feeder of
[0080] The same circuit then was simulated replacing the converters on the two buses with ideal DC sources. The voltages of the DC sources were set at the pre-fault voltages of Bus 1 and Bus 2 of the DC feeder with converters. The current from Bus 1 to fault from the circuit with the ideal DC source was plotted in
C. Fault Detection and Fault Location
[0081] Detecting a fault is necessary before applying the proposed method to locate it. This Section shows how Eq. 13 can be used for fault detection as well. If voltage drop per unit length of line is denoted as vu(t), i.e.,
Eq. 13 becomes
[0082] Under normal loading condition, as seen in
[0083] But v.sub.1(t)=L.sub.line*v.sub.u(t)+v.sub.2(t), where L.sub.line is the length of the line. So,
[0084] Eq. 17 implies that under normal operation, the calculated length of fault point from Bus 1 will be larger than the line length. In case of Bus 2, the current in the line is flowing towards the bus. As a result, from the perspective of Bus 2, both the measured current i.sub.2(t) and the voltage drop per unit length of line, v.sub.u(t) are negative. So, from Eq. 16, x becomes a negative number under normal operating condition. Thus, under unfaulted condition, the distance measured will be either greater than the line length or negative. This can be used to distinguish pre-fault condition from fault condition, and hence, can detect a fault. Note that the pre-fault current has to be used with care in this approach. Since the load current can change over time, the pre-fault current should be updated with every new sample if no fault is detected. But, once a fault is detected, the pre-fault current should be fixed at its latest updated value during the fault location process.
D. Results
[0085] To implement methodology herewith, especially as represented by algorithm and flowchart information presently disclosed, one or more processors may be provided, programmed to perform the steps and functions called for by the algorithm and flowchart information, as will be understood by those of ordinary skill in the art.
[0086] To evaluate the performance of the algorithm developed in Section IV-C, data were generated from the fault simulation described in Section IV-B with sampling frequency of 1 MHz. To implement the flowchart of
[0087] The accumulated data spanned from 40 μs before the fault inception to 80 ∞s after. From the 3rd sample after the fault inception time to the end of accumulated data, the calculated distances from Bus 1 varied from 79.8 m to 81.4 m. Thus, the proposed method provides accurate fault location over an extended range of data points after fault.
E. A Special Case
[0088] Clearly, the derivation of theory assumes DC sources present at both ends of the feeder. Since most of the DC loads and all non-ideal sources connect through converters, this is a reasonable assumption. A DC bus with only purely resistive load is therefore a rare case. However, it should be mentioned that under this unlikely scenario, one of the sources in
[0089] It is important to mention here that the DC feeder analyzed here would typically be a part of a DC microgrid. This special case can occur only if such microgrid is single-sourced and there is no converter-based load in the microgrid. This is contrary to the very nature of microgrids, and therefore, this special case would be rare in practice.
V. Using the Method for High Resistance Faults
[0090] In order to use the method for high resistance faults, the impact of higher fault resistance on the fault-induced transient needs to be understood. From Eq. 3, fault current in a feeder fed by an ideal source is
where, τ.sub.T is the equivalent time constant, and
[0091] Also, τ.sub.T=L/R=time constant of line, and
[0092] From Eq. 19, τ.sub.T is smaller than both τ.sub.L and τ.sub.f. The smaller the value of τ.sub.T, shorter the time the transient will last. Therefore, as the value of R.sub.f increases, the transient period will be shorter.
[0093] According to the IEEE Power System Relaying Committee report.sup.[31], a fault is considered a high impedance fault if it results in currents comparable to load currents, not detectable by traditional overcurrent relays or fuses. Based on the converter rating of 400 V, 100 kW, the corresponding load current and load resistance are 250 A and 1.6Ω, respectively. Therefore, any fault with resistance 1.6Ω or higher is considered a high resistance fault for this system.
[0094] A fault is simulated in the system described in Section IV-A with R.sub.f=2Ω, at fault inception time t.sub.0=0.1 s, at a distance of 80 m from Bus 1. From the manufacturer's data sheet of the chosen 185 sq mm conductor.sup.[33], τ.sub.L≈2955.6 μs and τ.sub.f≈2.3432 μs. According to Eq. 19, τ.sub.T≈2.34 μs. According to the literature.sup.[32], the transient will settle down approximately within 5τ.sub.T≈11.71 μs after the fault inception. The current plot in
[0095] Observe from the voltage plot of
[0096]
[0097] Clearly, there is a significant error in fault location. This is because errors are introduced in the calculation of di/dt due to the much steeper exponential transient. To minimize this error, a higher sampling frequency is required. Table IV confirms this rationale. Conversely, it can be argued that lower sampling rates would suffice for faults with low fault resistances. In the fault simulation case with R.sub.f=0.01Ω in Section IV-B, data were sampled at 1 MHz frequency. The same circuit was simulated and sampled at lower frequencies and the proposed algorithm was implemented for the same amount of time to check the performance of this method at lower frequencies. Table V shows the results. Data points from lower sampling frequency cases result in higher error, but even with 100 kHz sampling frequency, the error is less than 5%. These results illustrate that as long as the sampling frequency is adequate, the proposed method provides accurate results regardless of fault resistance.
[0098] To further investigate the performance of the method for high resistance faults, faults with resistances ranging from 0.01Ω to 100Ω were simulated. Table III lists the sampling frequencies required to get the fault location error within ±1.5%. These results illustrate that as long as the sampling frequency is adequate, the proposed method provides accurate results, regardless of fault resistance. The state-of-the-art oscilloscopes have probes that can sample up to 100 GHz.sup.[19], which would enable the method to work for higher fault resistance values as well.
[0099] It should be mentioned that all the faults considered were purely resistive. In AC distribution systems, High Impedance Fault (HIF) has a complex model with non-linear elements like diodes and variable resistors, to capture the results obtained by staged faults.sup.[39]. This model represents the arcing that almost always accompanies such faults, which, depending on the ground-surface in the fault path, changes significantly, producing different amounts of heat, making the fault resistance change randomly. Such models have not been developed for faults on low voltage DC circuits, and hence out of scope of this disclosure.
VI. Sensitivity Analysis
A. Fault Distance
[0100] As
the less L.sub.1 or L.sub.2 will be, the less L.sub.p will become, which will eventually result in lower τ.sub.f. So, if the fault is very close to or very far from the bus, τ.sub.f will be smaller, and according to the trend seen in Section V, errors will be higher, potentially requiring higher sampling frequency. To examine the sensitivity of the method to fault distance, several simulations were performed with varying fault distances and R.sub.f=0.01Ω in the system of
B. DC Link Capacitor Size
[0101] The proposed fault location method is accurate because the DC link capacitor behaves like an ideal DC source for a short duration after the initiation of a fault; however, the time duration for which the response of the capacitor can be treated as the response of an ideal DC source is dependent on the size of the capacitor. Given the fault resistance, line parameters, and fault distance is fixed, this duration gets larger if the capacitor size (in Farad) gets larger. With the advancement in power electronics and high-speed switching devices, the capacitor size used at the output of converters is getting reduced since the high-speed switching devices can support higher switching frequency. Thus, it is important to check how the method performs with lower values of DC link capacitance.
[0102] A general approach to calculating the size of the output capacitor of a DC-DC boost converter is to use the concept of charge balance. According to this concept, during steady state, the average change of the stored charge and, hence, the average change in the capacitor voltage will be zero over a switching period. From Eq. 20, which can be derived from prior publications.sup.[30,38], the minimum capacitance C required to restrict the ripple at the converter output within Δv.sub.max can be obtained.
[0103] Here, 2Δv.sub.max=ripple voltage (peak-to-peak), I=average inductor current, C=DC-link capacitor value, and T.sub.s=switching-period.
[0104] Several simulations were performed in the circuit of
VII. Conclusion
[0105] This disclosure develops a deterministic closed-form mathematical model based on the time-domain physical model of a faulted DC feeder. It is shown that as long as the sampling frequency is high enough to enable accurate calculation of the current derivative (di/dt), the single-ended fault detection and location method derived from this model is immune to fault resistance. This overcomes a well-known hurdle encountered in all single-ended fault location methods proposed in literature. The method is shown to work even when the feeder is fed by converter-based practical DC sources. The detection and location happen simultaneously in 3 samples after inception of fault, which translates to 3 μs for a sampling rate of 1 MHz. This assures the safety of circuit breakers as well as converters. The method works well even for high resistance faults, if the sampling frequency can be increased, a condition that is not unreasonable with the technology available today, as oscilloscopes in the market.sup.[19] support sampling frequency of up to 100 GHz. Since the purpose of this disclosure is to disseminate the seminal theory that enables this application, a single DC feeder is simulated for validation. Future work will be focused on extending the application to build a coordinated protection scheme for an entire DC microgrid.
[0106] Moreover, this disclosure reports the discovery of the mathematical foundations and implementation of a fast fault location method for a DC feeder that is independent of the topology of the system built around the feeder. This opens the doors for a communication-free topology-independent protection scheme for an entire DC microgrid. Such a scheme could use the presently disclosed method as a time-domain distance relay, placed on each side of every feeder of a DC microgrid. It could also be possible to adapt the performance of the presently disclosed method for different grounding schemes in a DC microgrid. Further research can be performed to include feeder capacitance in the formulation to adapt the method for HVDC lines fed by voltage source converters (VSCs).
[0107] While the present subject matter has been described in detail with respect to specific example embodiments thereof, it will be appreciated that those skilled in the art, upon attaining an understanding of the foregoing may readily produce alterations to, variations of, and equivalents to such embodiments. Accordingly, the scope of the present disclosure is by way of example rather than by way of limitation, and the subject disclosure does not preclude inclusion of such modifications, variations and/or additions to the present subject matter as would be readily apparent to one of ordinary skill in the art.
REFERENCES
[0108] [1] H. Kakigano, Y. Miura, and T. Ise, “Low-voltage bipolar-type DC microgrid for super high quality distribution,” IEEE Transactions on Power Electronics, vol. 25, no. 12, pp. 3066-3075, 2010. [0109] [2] L. Kong, H. Nian, Q. Huang, Z. Zhang, J. Xu, and K. Dai, “Optimization of current breaker and fault current limiter in DC micro-grid based on faulty transient analysis,” in 2018 21st International Conference on Electrical Machines and Systems (ICEMS), 2018, pp. 2017-2022. [0110] [3] A. Meghwani, S. C. Srivastava, and S. Chakrabarti, “Local measurement based technique for estimating fault location in multi-source DC microgrids,” IET Generation, Transmission Distribution, vol. 12, no. 13, pp. 3305-3313, 2018. [0111] [4], “A non-unit protection scheme for DC microgrid based on local measurements,” IEEE Transactions on Power Delivery, vol. 32, no. 1, pp. 172-181, 2017. [0112] [5] A. Ukil, Y. M. Yeap, and K. Satpathi, Fault Analysis and Protection System Design for DC Grids, 1st ed. Singapore: Springer Nature Singapore Pte Ltd, 2020. [0113] [6] R. Bhargav, B. R. Bhalja, and C. P. Gupta, “Novel fault detection and localization algorithm for low-voltage DC microgrid,” IEEE Transactions on Industrial Informatics, vol. 16, no. 7, pp. 4498-4511, 2020. [0114] [7] C. Noh, C. Kim, G. Gwon, and Y. Oh, “Development of fault section identification technique for low voltage DC distribution systems by using capacitive discharge current,” Journal of Modern Power Systems and Clean Energy, vol. 6, no. 3, pp. 509-520, 2018. [0115] [8] C. Yuan, M. A. Haj-ahmed, and M. S. Illindala, “Protection strategies for medium-voltage direct-current microgrid at a remote area mine site,” IEEE Transactions on Industry Applications, vol. 51, no. 4, pp. 2846-2853, 2015. [0116] [9] M. Monadi, C. Gavriluta, A. Luna, J. I. Candela, and P. Rodriguez, “Centralized protection strategy for medium voltage DC microgrids,” IEEE Transactions on Power Delivery, vol. 32, no. 1, pp. 430-440, 2017. [0117] [10] A. Meghwani, S. C. Srivastava, and S. Chakrabarti, “A new protection scheme for DC microgrid using line current derivative,” in 2015 IEEE Power Energy Society General Meeting, 2015, pp. 1-5. [0118] [11] A. Meghwani, S. Chakrabarti, and S. C. Srivastava, “An on-line fault location technique for DC microgrid using transient measurements,” in 2017 7th International Conference on Power Systems (ICPS), 2017, pp. 386-391. [0119] [12] R. Mohanty, U. S. M. Balaji, and A. K. Pradhan, “An accurate noniterative fault-location technique for low-voltage DC microgrid,” IEEE Transactions on Power Delivery, vol. 31, no. 2, pp. 475-481, 2016. [0120] [13] A. K. Pradhan and R. Mohanty, “Cable fault location in a DC microgrid using current injection technique,” in 2016 National Power Systems Conference (NPSC), 2016, pp. 1-6. [0121] [14] O. M. K. K. Nanayakkara, A. D. Rajapakse, and R. WAChal, “Traveling wave-based line fault location in star-connected multiterminal hvDC systems,” IEEE Transactions on Power Delivery, vol. 27, no. 4, pp. 2286-2294, 2012. [0122] [15] S. Azizi, M. Sanaye-Pasand, M. Abedini, and A. Hasani, “A traveling wave-based methodology for wide-area fault location in multiterminal DC systems,” IEEE Transactions on Power Delivery, vol. 29, no. 6, pp. 2552-2560, 2014. [0123] [16] S. Beheshtaein, R. M. Cuzner, M. Forouzesh, M. Savaghebi, and J. M. Guerrero, “DC microgrid protection: A comprehensive review,” IEEE Journal of Emerging and Selected Topics in Power Electronics, pp. 1-1, 2019. [0124] [17] Q. Yang, J. Li, S. Le Blond, and C. Wang, “Artificial neural network based fault detection and fault location in the DC microgrid,” Energy Procedia, vol. 103, pp. 129 — 134, 2016, renewable Energy Integration with Mini/Microgrid—Proceedings of REM2016. [Online]. Available: http://www.sciencedirect.com/science/article/pii/S1876610216314710 [0125] [18] SEL-T400L Time-Domain Line Protection, SEL, Accessed Feb. 14, 2021 [pdf]. [Online]. Available: https://cms-cdn.selinc.com/assets/Literature/Product%20Literature/Data%20Sheets/T400L DS 20190430.pdf?v=20190508-132121 [0126] [19] Digital and Mixed Signal Oscilloscopes, Tektronix, Accessed Jan. 28, 2021 [pdf]. [Online]. Available: https://www.tek.com/datasheet/digital-and-mixed-signal-oscilloscopes [0127] [20] S. D. A. Fletcher, P. J. Norman, S. J. Galloway, P. Crolla, and G. M. Burt, “Optimizing the roles of unit and non-unit protection methods within DC microgrids,” IEEE Transactions on Smart Grid, vol. 3, no. 4, pp. 2079-2087, December 2012. [0128] [21] S. D. A. Fletcher, P. J. Norman, K. Fong, S. J. Galloway, and G. M. Burt, “High-speed differential protection for smart DC distribution systems,” IEEE Transactions on Smart Grid, vol. 5, no. 5, pp. 2610-2617, 2014. [0129] [22] M. Mobarrez, D. Fregosi, S. BhattACharya, and M. A. Bahmani, “Grounding architectures for enabling ground fault ride-through capability in DC microgrids,” in 2017 IEEE Second International Conference on DC Microgrids (ICDCM), 2017, pp. 81-87. [0130] [23] D. Salomonsson, L. Soder, and A. Sannino, “Protection of low-voltage DC microgrids,” IEEE Transactions on Power Delivery, vol. 24, no. 3, pp. 1045-1053, 2009. [0131] [24] Y. Reddy O, S. Chatterjee, A. K. Chakraborty, and A. R. Bhowmik, “Fault detection and location estimation for lvDC microgrid using self parametric measurements,” International Transactions on Electrical Energy Systems, vol. n/a, no. n/a, p. e12499. [Online]. Available: https://onlinelibrary.wiley.com/doi/abs/10.1002/2050-7038.12499 [0132] [25] Service Cable Products, Nexans Energy, Accessed Feb. 3, 2020 [pdf]. [Online]. Available: https://drive.google.com/file/d/1q Brt1anpfkm1p7ashIYUGqg5kBVu2 BP/view?usp=sharing [0133] [26] S. Augustine, J. E. Quiroz, M. J. Reno, and S. Brahma, “DC microgrid protection: Review and challenges,” Sandia National Laboratories, New Mexico, USA, Tech. Rep. SAND2018-8853, August 2018. [0134] [27] T. R. de Oliveira, A. S. Bolzon, and P. F. Donoso-Garcia, “Grounding and safety considerations for residential DC microgrids,” in IECON 2014-40th Annual Conference of the IEEE Industrial Electronics Society, 2014, pp. 5526-5532. [0135] [28] G. M. Masters, Renewable and Efficient Electric Power Systems, 2nd ed. Hoboken, New Jersey: John Wiley & Sons, 2013, ch. 3, sec. 9.2, p. 174. [0136] [29] T. Kaipia, P. Nuutinen, A. Pinomaa, A. Lana, J. Partanen, J. Lohjala, and M. Matikainen, “Field test environment for IvDC distribution—implementation experiences,” in CIRED 2012 Workshop: Integration of Renewables into the Distribution Grid, 2012, pp. 1-4. [0137] [30] S. D. A. Fletcher, P. J. Norman, S. J. Galloway, and G. M. Burt, “Determination of protection system requirements for DC unmanned aerial vehicle electrical power networks for enhanced capability and survivability,” IET Electrical Systems in Transportation, vol. 1, no. 4, pp. 137-147, 2011. [0138] [31] “High impedance fault detection technology,” PSRC Working Group D15, Tech. Rep., Accessed Aug. 23, 2020 [pdf]. [Online]. Available: https://www.pes-psrc.org/kb/published/reports/High Impedance Fault Detection Technology.pdf [0139] [32] J. W. Nilsson and S. A. Riedel, Electric Circuits, 9th ed. One Lake Street, Upper Saddle River, New Jersey: Prentice Hall, 2011, ch. 7, sec. 7.1, p. 217. [0140] [33] LT/HT Power & Control Cables, HAVELLS, Accessed Jun. 5, 2021[pdf]. [Online]. Available:https://www.havells.com/content/dam/havells/brouchers/Industrial%20Cable/Cable%20Catalogue-2016.pdf[25] [0141] [34] X. Feng, L. Qi, and J. Pan, “A novel fault location method and algorithm for DC distribution protection,” IEEE Transactions on Industry Applications, vol. 53, no. 3, pp. 1834-1840, 2017. [0142] [35] J. E. Hill, S. D. Fletcher, P. J. Norman, and S. J. Galloway, “Protection system for an electrical power network,” Sep. 23, 2014, U.S. Pat. No. 8,842,401. [0143] [36] J.-D. Park, “Fault detection, isolation, location and reconnection systems and methods,” Apr. 14 2015, U.S. Pat. No. 9,007,735. [0144] [37] B. Hauke, “Basic calculation of a boost converter's power stage,” Texas Instruments, Texas, USA, Tech. Rep. SLVA372C, Nov 2009. [Online]. Available: https://www.ti.com/lit/an/sIva372c/sIva372c.pdf?ts=1642440495717 [0145] [38] R. W. Erickson and D. Maksimovic, Fundamentals of power electronics, 3rd ed. Springer International Publishing AG, 2020. [0146] [39] S. Gautam and S. M. Brahma, “Detection of high impedance fault in power distribution systems using mathematical morphology,” IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 1226-1234, 2013.
APPENDIX A
[0147] DETAILED PROOF OF FAULT CURRENT EXPRESSION IN DC MICROGRIDS WITH IDEAL VOLTAGE SOURCES Applying KVL in loop 1 for
Similarly in loop 2,
From equations 1 and 2 we can get
Putting the values of Δ.sub.1 and Δin eqn. A1 I.sub.1 can be expressed as
Let's say the denominator of eqn. A5 is (L.sub.1L.sub.2)*(as.sup.2+bs+c) where
Roots of as.sup.2+bs+c=0 are
where, 1/L.sub.p=1/L.sub.1+1/L.sub.2, parallel equivalent inductance of L.sub.1, L.sub.2. [0148] But, R.sub.1/L.sub.1=R.sub.2/L.sub.2=1/τ.sub.L=λ.sub.L, where τ.sub.L=time contant of line. [0149] Let's say λ.sub.f=1/τ.sub.L=F.sub.f/L.sub.p
[0150] So, from eqn. A.8
Now, roots from eqn. A.7
If eqn. A.5 is expanded through partial fraction expansion and subsequent inverse Laplace transform is done on that, the current expressions will get the following forms.
[0151] It can be shown that, in eqn. A.14 the coefficient K.sub.2=0. The coefficient K.sub.2 will be
Numerator of eqn. A15 can be reorganized as follows
From the prefault circuit I.sub.0=(V.sub.1−V.sub.2)/R, so the numerator comes
When evaluated at s=−λ.sub.L, the numerator becomes
[0152] But from line parameter, R.sub.2/L.sub.2=R/L, i.e., R.sub.2=RL.sub.2/L. So the numerator becomes
[0153] This means coefficient K.sub.2=0 and eventually current i.sub.1(t) reduces to
[0154] So the current i.sub.1(t) can be represented through one exponent. In a similar fashion, expression for i.sub.2(t) can be derived and written as
APPENDIX B
CALCULATION OF COEFFICIENTS
[0155] In this section, coefficients K.sub.1 and K.sub.2 are calculated for section III using the relevant data. From eqn. A13