Bump-less transfer term for proportional action controllers that eschew the integral action term
09651923 ยท 2017-05-16
Inventors
Cpc classification
International classification
Abstract
In automatic process-control systems, the integral action term in Proportional plus Integral action (P+I) control is used primarily to prevent any continued deviations from a set-point, and concomitantly to secure a bump-less transfer from manual control to automatic control. However, there are serious set-backs when using the integral action term for level controls, due to the liability of the integral action term to cause overflows from vessels, which can result in disastrous oil-spills, when a process is on automatic control. Hence, to secure a bump-less transfer without the integral action term, an alternate method is necessary. The method advocated calls for an additional term, which has been termed as a Bump-less Transfer BT(t) term, to be included into the control algorithm. This term accepts deviations from the set-point, and even brings about sufficient deviation from the set-point to secure a bump-less transfer, since deviations within the proportional band are normally acceptable for level controls.
Claims
1. A method of securing a bump-less transfer from manual control to automatic control for processes controllers, comprising a term that secures a bump-less transfer without using Proportional plus Integral action controllers, known by the acronyms P+I or PI controllers, for level controls, and using only Proportional action controllers for said controls, due to the liability of the integral action term to cause overflows from vessels, occasionally disastrous oil-spills, when a process is on automatic control, because control at a set-point, which necessitates the integral action term, is not required for level controls, by including in the place of the integral action term, which had conveniently also served to secure a bump-less transfer, a novel Bump-less Transfer BT(t) term into the control algorithm, which enables a bum-less transfer, by bringing the level in the vessel to the level required for a bump-less transfer, while keeping the bias value B fixed at its necessary 50% value; via said BT(t) term having two components: 1) an initial magnitude, 2) a bleed rate; with the initial magnitude of said BT(t) term, determined automatically, by the inclusion of an equation for the automatic determination of said BT(t) term, in the distributed control system (DCS) of the assigned computer, which said BT(t) term, is the difference in value between said process value PV(t), in percent (time varying), which said process is said level in said vessel, and the manual value of output in percent, OP(m), and thus the basic equation for automatically determining the initial magnitude of said BT(t) term for a direct acting controller is as follows:
BT(t)=OP(m)K(PV(t)SP)B with the value of B fixed at 50%, and the basic equation for automatically determining the initial magnitude of said BT(t) term for a reverse acting controller is as follows:
BT(t)=OP(m)+K(PV(t)SP)B with the value of B fixed at 50%, while the bleed rate, being the time taken for the magnitude of said BT(t) term to fall from its initial value to zero, is set externally by the process control engineer, in the same way the set-point SP, and the gain K of a controller are set, is preset a default value of 5 minutes.
2. The method of claim 1, but wherein, said BT(t) term is incorporated into said bias B, during said preset period of time for transfer from manual to automatic control, as follows: the said bias B itself is moved to match the value required for a bump-less transfer, and then is brought back to the required 50% value, within a fixed preset period of time, and so, said BT(t) term, need not be as a separate entity, but is instead incorporated into the said bias B, for said preset period of time required for the said transfer from manual control to automatic control, and so would appear for said preset period of time, as a varying bias, and thus for direct acting controllers, said bias B, would, for said preset period of time, be BT(t)+B, and for reverse acting controllers, said bias B, would, for said preset period of time, be BT(t)B.
3. The method of claim 1, wherein, because the said bump-less transfer term, BT(t), does not ensure a totally bump-free transfer of control from manual control to automatic control, a manual method is employed, which manual method calls for the required level, the level in the said vessel should be brought to, deduced from the said manual output, OP(m), said level is manually brought to, through manual facilities, wherever needed, before it is transferred to automatic control to make the transfer utterly bump-less.
Description
BRIEF DESCRIPTION OF THE DRAWINGS
(1)
(2)
(3)
(4)
DETAILED DESCRIPTION OF THE INVENTION
(5) Whenever a process control system is transferred from manual control to automatic control it is generally required to make the transfer bump-less, i.e. ensuring there is no change in process values when the transfer from manual control to automatic control is made.
(6) For proportional plus integral action control and proportional plus integral plus derivative action (PID) control, there is no difficulty in achieving this, because the integral action term can smoothly accomplish this. However, for proportional action only (P only) controllers, and proportional plus derivative (P+D) action controllers no such smooth solution exists at present.
(7) Hence, makers of Distributed Control Systems (DCS) do not provide an easy, convenient way to secure bump-less transfers for such controllers, suitable for the plant operators. However, when they claim they do, they go about it in the wrong way, leading to lopsided controls, often to the confusion and dismay of the unsuspecting user.
(8) In order to explain the preferred embodiment for a bump-less transfer for a proportional controller without integral action according to the present innovation, it is necessary to resort to a mathematical description. In the formulae used the terms employed are defined as follows: OP(t) Output of the controller in percent (time varying) OP(m) Manual value of Output in percent K Gain of the controller PV(t) Process Value in percent (time varying) SP Set Point in percent BT(t) Bump-less Transfer term in percent (time varying) B Bias value in percent (normally 50%) T Sampling interval OPn Output in percent at the nth sampling interval Td Derivative action time T.sub.i Integral action time BT.sub.n Bump-less Transfer term at the nth sampling interval e.sub.k error (PVSP) at the kth sampling interval e.sub.n error (PVSP) at nth sampling interval e.sub.n-1 error (PVSP) at (n1) th sampling interval
(9) The output of a direct acting proportional controller follows the equation:
OP(t)=K(PV(t)SP)+B(1)
(10) While the output of a reverse acting proportional controller follows the equation:
OP(t)=K(PV(t)SP)+B(2)
(11) For a good control system, it is essential that the bias value B be kept at 50%, as can be seen from the several graphs shown in
(12) The additional term BT(t) in the control equation has a magnitude as well as what may be called as the bleed rate. This bleed rate is given in minutes or in seconds, and it should be set, like integral and derivative action rates by the process control engineer. The initial value of BT(t) depends on the manual value of the output before the bump-less transfer to automatic control. Hence, the magnitude of BT(t) is internally set, and is not externally set as its bleed rate.
(13) Thus, the control equation for a direct acting proportional controller becomes as follows:
OP(t)=K(PV(t)SP)+B+BT(t)(3)
(14) While, for a reverse acting proportional controller the equation becomes as follows:
OP(t)=K(PV(t)SP)+B+BT(t)(4)
(15) Where the initial magnitude of BT(t) is set internally, and is dependent on the manual value of output before bump-less transfer to automatic control. Hence, if PV(t) =SP, and the value of the manual output OP(m) were to be 75%, the magnitude of BT(t) will automatically be internally set as follows:BT(t)=OP(m)B=75%50%=25%. However, the bleed rate of BT(t) will be set externally by the process control engineer. The bleed rate determines how slowly or quickly the magnitude of BT(t) falls at the same rate from its initial value to zero. Once the magnitude of BT(t) is reduced to nothing, it remains zero for the rest of the time the system is on automatic control.
(16) For a better understanding, the sampled data discrete DCS form of the equations using the Bump-less Transfer term BT(t) is now compared with controllers having the integral action term, as controllers with integral action do not require the BT(t) term.
(17) The equations for these are given below for the direct acting controllers:
(18)
(19) From the equation of the P+I controller it can be seen how the output can be easily varied to match the manual output by varying the error value summation in the integral action term without varying B the bias value. Hence, the bias value of 50% need not be compromised. However, for P only control, this facility is not available for bump-less transfer from manual control to automatic control. Thus the need for the additional BT(t) term to facilitate the transfer, but in some DCS, as stated earlier, the bias value appears to have been varied, because of the unavailability of the integral action term in P only control. This brings about a lopsided control, as may be seen in
(20) These programmers are apparently not fully conversant with control theory and do not realize that they have brought on a lopsided control, since they may go unidentified in P+I controllers, in spite of them setting an irremediable error for the setting of suitable integral action times. However, for P only controllers the consequence will be totally unacceptable as shown in
(21) P+D controllers are rarely used, as whenever derivative action is used the integral term is invariably used. Further, the transfer from manual control to automatic control is usually done in the steady state. Hence, there will be no difference in the error at the nth sampling interval and the (n1)th sampling interval, and so the derivative action term will be zero. If this is not so, it is still advisable to neglect the term as it is small. Hence, at this stage it can be quite insignificant. However, for purely academic reasons, and if it is not ignored, the initial value of BTn for a direct acting controller would be as follows:
BTn=OP(m)BKe.sub.nKTd/T(e.sub.ne.sub.n-1)(with B=50%)(7)
(22) Some may be of the view, that because of the difficulty in securing bump-less transfer for proportional control without integral action, why not, always have proportional plus integral action, or at least whenever it required to have bump-less transfer from manual control to automatic control. However, integral action has a serious side effect, which makes it not always that desirable. Let us therefore examine what this is. The primary reason for having integral action is to eliminate offset. Hence, it was originally known as reset action.
(23) However, the side effect is, when there is a process change, because of the integral action term it is unable to respond proportionately at once to the process change. This, in some cases can lead to oscillations about the set point while trying to arrive at the set point, or to even a process upsets. Thus, proportional control without integral action is sometimes necessary to bring about stability to a system. In the case of level control, it can also lead to an overflow from a vessel or to its emptying. To overcome this, an increase in vessel height, with width unchanged, may be required for P+I control than when using proportional only control. Further, as it is often hard to find a suitable integral action time, it is best to avoid integral action, unless control without offset is essential.
(24) Since in the control of level, precise control at a particular level is very rarely needed, proportional control without integral action is almost always used for greater stability. Hence, for a further understanding of this novel method of control using the additional term BT(t) for bump-less transfer, a level control application will now be considered. Suppose, for a certain flow into a tank, the control valve has to be opened 75%, so that the level in the tank neither rises or falls, then the output to the control valve has to be 75%. Thus, if a plant operator had brought the level to 50% as shown in
BT(t)=OP(m)K(PV(t)SP)B(for a direct acting controller)(8)
(25) Now, suppose the bleed rate of BT(t) is set at 5 minutes, then as the magnitude of BT(t) falls, the value of OP(t) also falls, causing the valve to close slightly. This in turn causes the level to rise, which in turn will cause PV(t) to be greater than SP. This will increase the value of OP(t). Thus slowly after 5 minutes the magnitude of BT(t) would be reduced to zero from its initial value set internally at 25%. However, since the value of PV(t) would have risen to 75%, by the time BT(t) had fallen to zero, for a direct acting proportional controller with a gain of 1, the output remains at 75% as can be seen in the following equation:
OP(t)=K(PV(t)SP)+B=1(7550)+50=75.(9)
(26) The equation also shows there will be an offset from the Set Point. However, this offset of 25% from the set point is perfectly acceptable for a proportional only controller that has a gain of one.
(27) For a fuller understanding of the problems involved, and how by using the new BT(t) term the present shortcomings are overcome,
(28)
(29)
(30)
(31)
(32) Although the invention has been explained in relation to its preferred embodiment, it is to be understood that other possible modifications and variations can be made without departing from the spirit and scope of the invention as hereinafter claimed.