Building Panel Assembly and Method of Manufacturing
20180298600 ยท 2018-10-18
Inventors
Cpc classification
E04B1/18
FIXED CONSTRUCTIONS
E04C2/388
FIXED CONSTRUCTIONS
E04C2/296
FIXED CONSTRUCTIONS
B29K2075/00
PERFORMING OPERATIONS; TRANSPORTING
E04B1/14
FIXED CONSTRUCTIONS
B29L2031/10
PERFORMING OPERATIONS; TRANSPORTING
E04B1/6145
FIXED CONSTRUCTIONS
E04C2/292
FIXED CONSTRUCTIONS
International classification
E04B1/14
FIXED CONSTRUCTIONS
E04C2/292
FIXED CONSTRUCTIONS
E04B1/61
FIXED CONSTRUCTIONS
E04B1/41
FIXED CONSTRUCTIONS
E04C2/296
FIXED CONSTRUCTIONS
E04B1/18
FIXED CONSTRUCTIONS
Abstract
The invention comprises building panel assemblies for use in the construction of new homes, commercial buildings and extensions of one or more storeys. There is provided a rectangular structural insulated panel (SIP) (10), which comprises a pair of spaced-apart containment boards (12, 12) an inner insulating core (13) and a low profile peripheral external rigid frame (14), preferably of metal, e.g. steel, extending around the entire periphery of the spaced-apart boards (12, 12), the insulating core (13) having spaced-apart slots (16), which also extend around the entire periphery of the panel.
Claims
1. A building panel assembly comprising a pair of spaced-apart containment boards, separated by an inner insulating core, said inner insulating core having at least one peripherally disposed channel for receiving a rigid frame, said channel spaced apart from and disposed between the containment boards.
2. An assembly as claimed in claim 1 wherein, the frame defines a pair of spaced-apart longitudinal channels, which extend around the periphery of the panel and extend into the space between the spaced-apart pair of containment boards.
3. An assembly as claimed in claim 1 wherein the frame is integrally formed with the insulating core which extends over the frame.
4. An assembly as claimed in claim 2 wherein two or more panels can be connected by means of a mating member.
5. An assembly as claimed in claim 4 wherein the mating member has I or H cross section and is received by the one or more channels in the insulating core or rigid frame.
6. An assembly as claimed in claim 4 wherein, the mating members are universal columns.
7. An assembly as claimed in claim 6, wherein the additional support comprises I-section and/or H-section UC supports.
8. An assembly as claimed in any one of the previous claims claim 1 comprising at least one conduit disposed adjacent to and between the containment board and the inner insulating core.
9. An assembly as claimed in claim 8 having two conduits.
10. An assembly as claimed in claim 9 wherein each conduit is spaced apart from one another and disposed opposite one another and adjacent to its respective containment board.
11. An assembly as claimed in claim 1 further comprising an alignment track upon which panels may be disposed.
12. An assembly as claimed in claim 1, in which the containment boards are selected from oriented strand board, cement particle board magnesium oxide wall board, plywood, pressure treated plywood, steel, aluminium, fibre reinforced plastics, or metal, or composite sheeting.
13. An assembly as claimed in claim 1, in which the inner insulating core is comprised of expanded polystyrene foam, extruded polystyrene foam or polyurethane foam.
14. An assembly as claimed in claim 1, further including a sole plate, which is securable to a foundation or floor, and having upstanding alignment rails correspondingly spaced for insertion into the spaced-apart longitudinal channels on the bottom edge of a building panel assembly, in use.
15. An assembly as claimed in claim 1, in which a second panel is connectable to, and alignable with, a first panel, by means of a pair of alignment tracks, which engage in the respective spaced-apart longitudinal channels of the respective adjacent panels, in use.
16. An assembly as claimed in claim 1, in which a vertical rigid frame member is provided having correspondingly spaced alignment tracks for engagement in respective spaced-apart longitudinal channels on the edge of an adjacent panel.
17. An assembly substantially as described herein with reference to the accompanying drawings.
18. A method of manufacturing a building panel assembly as claimed in claim 1 comprising the use of a jig having a frame comprising a plurality of frame members, having at least one ridge extending substantially around the inner surface of the frame and means for releasably securing the frame members together to form the frame, such that once a panel has been formed, the frame members can be released and the panel removed from the jig.
19. A method as claimed in claim 18 wherein the frame has two ridges extending substantially around the inner surface of the frame.
20. A method as claimed in claim 18 wherein the frame has an inlet to allow the passage of inner insulating core material therethrough.
21. A jig for use in the method of claim 18.
Description
[0044] Referring now to the drawings,
[0045] The panel may additionally be modified to include a conduit 15 to enable services such as electrical cabling to be fed to or across a panel 10 without compromising its structural integrity (see
[0046] The profile of the peripheral frame 14 is such that its cross section is substantially H-shaped which assist in ensuring a neat and secure interconnection of the respective panels 10.
[0047] The peripheral frame 14 comprises four elongate members 20 which run along the length of each side of the SIP panel and four corner members 22. When assembled they form a rigid peripheral frame around the inner insulating core 13, providing structural support. The corner members help ensure that the panels do not twist and increase torsional rigidity.
[0048] The shape of the panel 10 can be any suitable for use in constructing a building or the like, such as square, rectangular, triangular.
[0049]
[0050]
[0051] Referring now to
[0052]
[0053]
[0054] A plurality of panels 10 can be assembled and aligned using the external rigid frame 14, with I-section or H-section universal columns. In order to continue this structure vertically, further panels 10 can be placed on top of one another with joists hung between opposed parallel external rigid frames provide a support base for flooring panels for the upper storey and tie together opposite walls of the structure.
[0055]
[0056] As can be seen from the above, the components of the building system provided primarily by the novel panel of the present invention, incorporating the rigid peripheral frame having spaced-apart slots 16 provides a reliable and robust method of construction, providing a substantially improved method of construction having accurately positionable panels with improved stability and load bearing capacity, improved thermal insulating properties by reducing thermal bridging and fire resistance, due to a provision of the double channel arrangement with locking alignment rails which maintain a tight air gap and thereby prevent the spread of fire and smoke, as well as enabling the internal conditions of a structure to be better and more efficiently controlled. Further, the peripheral frame enables, more readily, the use of magnesium oxide panels to provide further fire resistance.
[0057]
EXAMPLE 1
[0058] A series of structurally insulated wall panels referenced as 4 wall structurally insulated semi-SIP's were received from EcoMech for testing for racking resistance to BS EN594:2011 Timber StructuresTest Methods. Racking strength and stiffness of the panel was determined according to Section 6.5 of BS EN 594:2011
[0059] Each panel was of overall size 24002400 mm and comprised of a 1 mm pressed steel frame and corner boots with a 1 mm pressed steel soleplate and head binder. The structural splines consisted of 12 mm Multi Pro XS magnesium boards with two per panel joint at 95 mm wide. The panels had a BASF PU structural insulated foam core.
[0060] 21.2 m2.4 m9 mm thick Multi Pro XS Magnesium sheathing boards were bonded (full surface) to the inner core of structural PU insulation and the panels screwed at nominally 150 mm centres at the soleplate and head binder.
[0061] Three of the panels were tested with no applied vertical load and three tested with 5 kN vertical load.
[0062] Holes 100 mm in diameter were cut in the base rail of each of the racking panels, centred at the anchorage points of the base rig. M16250 mm long bolts were inserted through the holes with large steel plates attached (50 mm wide220 mm long10 mm thick), which were rotated through 90 degrees to span across the 2 bottom rail flanges.
[0063] The racking panel was bolted to the test rig through a long hardwood timber foundation plate such that the bottom rail was fixed down by five M16250 mm long bolts. The panel was laid flat in the test rig which had been bolted down to the laboratory strong floor. The panel was placed on Teflon coated steel packers to allow it to move freely when loading.
[0064] Hydraulic rams were fixed to the test rig at the panel header end such that they would be able to apply a vertical top load to the panel at 600 mm centres. In accordance BS EN 594:2011, linear voltage displacement transducers (LVDT) were fixed in place so as to record horizontal deflection at the head of the panel, at the base of the panel and to measure any uplift at the base of the panel.
[0065] Using hydraulic rams linked via a common manifold, a vertical pre-load of 1 kN was applied to the head binder at the 600 mm centres and maintained for 120 s. This load was then removed and the panel allowed a recovery period of 300 s before continuing the test. After the stabilising load cycle, a vertical load (0 kN and 5 kN, respectively) was applied to the head binder at 600 mm centres and maintained throughout the test procedure. The racking load was then applied at a loading rate such that 90% of the maximum load of the panel was achieved within 300 seconds 200 seconds.
Results
[0066] The Racking stiffness for each panel tested in accordance with section 6.5.1 of BS EN594: 2011 and the modes of failure is given in Table 1.
[0067] Graphs of applied racking load against deflection are given in Figs.
TABLE-US-00001 TABLE 1 Summary of Racking Load for Echo Mech Panel screwed and bonded at nominally 80 mm centres Racking Basic Test Vertical Top Strength Racking Racking Panel Load per Fmax Stiffness Resistance No Stud (kN) (KN) (N/mm) R.sub.b (KN/m) Mode of Failure 1 0 26.84 3334 5.25 Panel pulled away from 2 22.07 1766 base rail at the leading 3 23.10 1674 stud along with some failure of base rail Mean 24.00 2258 1 5 34.30 2192 3.23 Panel pulled away from 2 33.13 2217 base rail at the leading 3 32.54 2985 stud along with some failure of base rail Mean 33.32 2465
[0068] The test that the panels were subjected to, was an industry designed racking test for timber frame panels, which in themselves had a failure point built in to the test rig. The limitations of this type of test was apparent in the fact that the test did not truly test or reflect the much higher racking resistance that the panels of the present invention have over timber frame panels for which the jig and test method was designed.
[0069] However, it is to be appreciated that the results obtained in this test still showed a substantial increase in racking resistance over and above a similar sized timber framed panel.
Note: The Basic test racking resistance given in BS5268 part 6.1 for a double sheathed panel Incorporating a category 1 board is 2.52 kN/m.
EXAMPLE 2
[0070] A section of a panel in accordance with the present invention (SIEP system) 2.324 m2.324 m was sealed into a Plywood box, with all joints made airtight was sealed around each wall such that the external face of the panel was open to atmosphere. The total test area was 5.4 m.sup.2.
[0071] A fan was connected to the enclosure and the pressure within the enclosure allowed to stabilise at a static pressure of 50 Pa. The static pressure was measured using an electronic manometer. The airflow into the sample was then measured and used to calculate the air leakage rate.
TABLE-US-00002 TABLE 2 Air Leakage Air leakage Panel Velocity (m/s) Flow (l/s) Rate (m.sup.3/h (m.sup.3/h/m.sup.2) Test 1 panel 0.70 1.282 4.617 0.855 according to present invention
[0072] As guidance the CIBSE Guide (CIBSE Guide TM23:2000 Testing Buildings for Air Leakage) for an entire dwelling states good practice is a limit of 10 m3/h/m2 @ 50 Pa and best practice is 5 m3/h/m2 @ 50 Pa.
EXAMPLE 3
[0073] A panel in accordance with the present invention of overall size 12002400 mm and comprised perimeter framing sections mitred and retained together with corner jointing brackets. The corner brackets were inserted into the perimeter profiles, through fixed, and spot welded.
[0074] A 1.2 m2.4 m by 9 mm thick magnesium silicate based board was fixed to each face of the single panel using 5.5 mm diameter65 mm long HILTI coated self-drilling wing tip screws. The board was fixed to the panel at nominally 300 mm centres to the perimeter framework. The fixings were placed 20 mm from the board edges. A panel core of polyurethane (PU) foam was injected into the cavity created by perimeter profiles and panel facing sheets and adhered to these components by its own adhesive properties whilst curing. Oriented strand board, Grade3 (OSB/3), 45 mm wide11 mm thick, were fitted into the perimeter frame profile, as perimeter infill, along the head and base of each single panel.
[0075] The test panel was located onto the laboratory strong floor centrally under the 2000 kN servo assisted compressive strength machine (Dartec). In order to achieve eccentric loading the panels were supported on a 20 mm thick steel plate such that 40 mm of the width of the panel base was supported.
[0076] Three linear voltage displacement transducers (LVDTs) were fixed in place at quarter points on the vertical centreline of the panel such that any horizontal movement was recorded.
[0077] A load equal to the estimated dead load was applied to the panel and held for 30 minutes then released. Deflection readings were taken on application of the load, on immediate removal and after 15 minutes.
[0078] The dead load was applied again and held for 15 minutes then increased to the design load and held for 24 hours. Deflection readings were taken at 60 minute intervals. The load was then released and recovery deflection readings were taken immediately and after 15 minutes.
[0079] The panel was then loaded to failure with deflection readings taken at 20 kN increments.
Results
[0080] A summary of the failure loads and failure modes of each panel tested under axial load is given in Table 3.
[0081] A summary of the failure loads and failure modes of each panel tested under eccentric load is given in Table 4.
[0082] Load deflection graphs are given in
[0083] Load deflection data is given in Appendix A, Tables A1-A6.
[0084] All panels tested axially failed similarly by initial failure and debonding of the sheathing and compression of the OSB at the base at a similar load of around 200 kN.
[0085] All panels tested eccentrically failed similarly by initial failure and debonding of the sheathing and OSB followed by compression of the sheathing and OSB at the base at a similar load of around 150 kN.
TABLE-US-00003 TABLE 3 Summary of Performance under Axial Compressive Load Dead Design Failure Failure Load Load Load Load (kN/m) (kN/m) (kN) (kN/m) Mode of Failure 1 15 60 186.2 155.2 Delamination of sheathing from base of frame and crushing of internal OSB to base stud
TABLE-US-00004 TABLE 4 Summary of Performance under Eccentric Compressive Load Dead Design Failure Failure Panel Load Load Load Load Number (kN/m) (kN/m) (kN) (kN/m) Mode of Failure 1 15 60 145.3 121.1 Delamination of 2 15 60 163.2 136.0 sheathing and OSB 3 15 60 136.7 113.9 from frame, compressive failure of sheathing and OSB. Compression failure of perimeter steel stud Mean 148.4 123.7
TABLE-US-00005 TABLE A1 Load/Deflection Data for Axial Compressive Strength on SIEP - Panel 1 Top Mid Point Base Load Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.06 0.08 0.24 15 Hold 30 min 0.15 0.20 0.36 0 Release 0.13 0.18 0.19 0 Hold 15 min 0.12 0.18 0.18 15 Dead load 0.14 0.20 0.35 15 Hold 15 min 0.17 0.24 0.39 60 Design load 0.56 0.63 0.80 60 Leave 15 min 0.69 0.73 0.84 60 1 hour 0.77 0.81 0.90 60 2 hour 0.82 0.90 0.94 60 3 hour 0.87 0.96 0.97 60 4 hour 0.91 1.03 1.02 60 5 hour 0.93 1.07 1.04 60 6 hour 0.93 1.08 1.05 60 7 hour 0.98 1.10 1.07 60 8 hour 0.95 1.09 1.06 60 9 hour 0.95 1.10 1.07 60 10 hour 0.96 1.11 1.07 60 11 hour 0.95 1.10 1.06 60 12 hour 0.95 1.10 1.06 60 13 hour 0.95 1.11 1.06 60 14 hour 0.95 1.10 1.06 60 15 hour 0.95 1.09 1.05 60 16 hour 0.95 1.09 1.04 60 17 hour 0.95 1.08 1.04 60 18 hour 0.95 1.08 1.04 60 19 hour 0.94 1.08 1.03 60 20 hour 0.94 1.08 1.03 60 21 hour 0.94 1.07 1.03 60 22 hour 0.95 1.07 1.03 60 23 hour 0.94 1.08 1.03 60 24 hour 0.94 1.07 1.03 0 Release 0.65 0.58 0.66 0 Hold 15 min 0.61 0.56 0.64 0 Increase to failure 0.65 0.59 0.65 20 0.77 0.77 0.72 40 0.96 1.13 0.94 60 1.14 1.39 1.21 80 1.25 1.52 1.28 100 1.52 1.63 1.29 120 2.03 1.72 1.33 140 3.24 2.37 1.59 160 3.44 2.50 1.77 180 3.55 2.66 1.99
TABLE-US-00006 TABLE A2 Load/Deflection Data for Axial Compressive Strength on SIEP - Panel 2 Top Mid Point Base Load Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.62 0.60 0.36 15 Hold 30 min 0.65 0.62 0.38 0 Release 0.61 0.59 0.32 0 Hold 15 min 0.59 0.58 0.31 15 Dead load 0.64 0.65 0.39 15 Hold 15 min 0.67 0.69 0.42 60 Design load 1.04 1.09 0.84 60 Leave 15 min 1.12 1.18 0.92 60 1 hour 1.21 1.25 0.97 60 2 hour 1.24 1.29 1.01 60 3 hour 1.28 1.33 1.04 60 4 hour 1.32 1.36 1.06 60 5 hour 1.37 1.39 1.09 60 6 hour 1.40 1.42 1.11 60 7 hour 1.40 1.42 1.11 60 8 hour 1.41 1.43 1.11 60 9 hour 1.40 1.42 1.12 60 10 hour 1.41 1.44 1.11 60 11 hour 1.42 1.42 1.11 60 12 hour 1.45 1.42 1.12 60 13 hour 1.48 1.41 1.14 60 14 hour 1.47 1.42 1.13 60 15 hour 1.49 1.42 1.11 60 16 hour 1.52 1.43 1.11 60 17 hour 1.57 1.42 1.11 60 18 hour 1.62 1.42 1.12 60 19 hour 1.66 1.43 1.11 60 20 hour 1.69 1.42 1.10 60 21 hour 1.74 1.41 1.11 60 22 hour 1.79 1.42 1.11 60 23 hour 1.85 1.42 1.11 60 24 hour 1.95 1.43 1.11 0 Release 1.91 1.35 0.78 0 Hold 15 min 1.82 1.25 0.71 20 Increase to failure 2.14 1.50 0.94 40 2.49 1.74 1.13 60 2.76 1.98 1.25 80 2.98 2.13 1.34 100 3.09 2.14 1.35 120 3.23 2.15 1.35 140 3.45 2.15 1.32 160 3.90 2.45 1.47 179.7 Failure 4.06 2.11 0.48
TABLE-US-00007 TABLE A3 Load/Deflection Data for Axial Compressive Strength on SIEP - Panel 3 Top Mid Point Base Load Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.01 0.00 0.01 15 Hold 30 min 0.01 0.00 0.01 0 Release 0.09 0.05 0.02 0 Hold 15 min 0.09 0.06 0.03 15 Dead load 0.09 0.05 0.03 15 Hold 15 min 0.09 0.04 0.03 60 Design load 0.17 0.16 0.17 60 Leave 15 min 0.15 0.16 0.17 60 1 hour 0.16 0.17 0.19 60 2 hour 0.16 0.17 0.19 60 3 hour 0.16 0.17 0.19 60 4 hour 0.16 0.16 0.19 60 5 hour 0.16 0.15 0.18 60 6 hour 0.16 0.15 0.18 60 7 hour 0.14 0.15 0.17 60 8 hour 0.13 0.12 0.14 60 9 hour 0.13 0.11 0.14 60 10 hour 0.14 0.12 0.15 60 11 hour 0.14 0.13 0.15 60 12 hour 0.15 0.13 0.16 60 13 hour 0.15 0.14 0.16 60 14 hour 0.15 0.14 0.17 60 15 hour 0.16 0.14 0.17 60 16 hour 0.16 0.14 0.17 60 17 hour 0.16 0.15 0.16 60 18 hour 0.16 0.15 0.17 60 19 hour 0.16 0.15 0.17 60 20 hour 0.16 0.15 0.17 60 21 hour 0.16 0.15 0.17 60 22 hour 0.16 0.15 0.17 60 23 hour 0.16 0.15 0.17 60 24 hour 0.16 0.15 0.17 0 Release 0.14 0.04 0.01 0 Hold 15 min 0.08 0.02 0.08 20 Increase to failure 0.06 0.05 0.13 40 0.06 0.06 0.18 60 0.06 0.02 0.08 80 0.08 0.01 0.05 100 0.17 0.07 0.02 120 0.32 0.17 0.06 140 0.54 0.35 0.14 160 0.79 0.53 0.23 178 1.56 1.00 0.91 188 1.61 0.79 0.88 200 2.18 0.90 0.86 210 2.24 0.83 0.74 220 2.70 0.77 0.64 226.5 Failure 4.61 2.55 2.44
TABLE-US-00008 TABLE A4 Load/Deflection Data for Eccentric Compressive Strength on SIEP - Panel 1 Top Mid Point Base Load Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.31 0.21 0.01 15 Hold 30 min 0.31 0.22 0.01 0 Release 0.00 0.04 0.03 0 Hold 15 min 0.31 0.23 0.02 15 Dead load 0.43 0.31 0.01 15 Hold 15 min 0.45 0.32 0.00 60 Design load 1.38 1.48 0.83 60 Leave 15 min 1.39 1.50 0.85 60 1 hour 1.43 1.55 0.91 60 2 hour 1.43 1.56 0.94 60 3 hour 1.43 1.58 0.96 60 4 hour 1.43 1.59 0.97 60 5 hour 1.43 1.59 0.99 60 6 hour 1.43 1.60 0.99 60 7 hour 1.43 1.60 0.98 60 8 hour 1.43 1.60 0.99 60 9 hour 1.43 1.60 0.98 60 10 hour 1.43 1.60 0.98 60 11 hour 1.43 1.60 0.98 60 12 hour 1.43 1.60 0.99 60 13 hour 1.43 1.59 0.98 60 14 hour 1.43 1.60 0.98 60 15 hour 1.43 1.60 0.98 60 16 hour 1.43 1.60 0.99 60 17 hour 1.43 1.60 0.98 60 18 hour 1.42 1.60 0.98 60 19 hour 1.43 1.59 0.99 60 20 hour 1.43 1.60 0.98 60 21 hour 1.43 1.60 0.98 60 22 hour 1.43 1.60 0.98 60 23 hour 1.43 1.60 0.98 60 24 hour 1.43 1.60 0.99 0 Release 0.41 0.34 0.05 0 Hold 15 min 0.38 0.33 0.03 20 Increase to failure 0.88 0.92 0.47 40 0.89 0.94 0.49 60 1.45 1.57 0.98 70 1.84 1.85 1.24 80 1.94 2.17 1.43 90 2.22 2.49 1.67 100 2.47 2.79 1.88 110 2.76 3.19 2.23 122 3.25 3.82 2.79 130 3.68 4.29 3.17 140 4.05 4.81 3.63 145.3 Failure 7.56 11.87 16.50
TABLE-US-00009 TABLE A5 Load/Deflection Data for Eccentric Compressive Strength on SIEP - Panel 2 Top Mid Point Base Load Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.18 0.09 0.00 15 Hold 30 min 0.19 0.10 0.00 0 Release 0.09 0.07 0.00 0 Hold 15 min 0.07 0.06 0.00 15 Dead load 0.17 0.09 0.01 15 Hold 15 min 0.19 0.12 0.02 60 Design load 1.29 0.93 0.40 60 Leave 15 min 1.40 1.01 0.44 60 1 hour 1.44 1.04 0.48 60 2 hour 1.47 1.07 0.50 60 3 hour 1.48 1.09 0.53 60 4 hour 1.49 1.10 0.54 60 5 hour 1.50 1.11 0.55 60 6 hour 1.51 1.12 0.56 60 7 hour 1.51 1.13 0.57 60 8 hour 1.51 1.13 0.58 60 9 hour 1.51 1.13 0.57 60 10 hour 1.50 1.12 0.57 60 11 hour 1.50 1.12 0.56 60 12 hour 1.50 1.12 0.57 60 13 hour 1.50 1.11 0.56 60 14 hour 1.49 1.12 0.57 60 15 hour 1.49 1.13 0.57 60 16 hour 1.50 1.12 0.57 60 17 hour 1.49 1.13 0.58 60 18 hour 1.49 1.13 0.59 60 19 hour 1.51 1.14 0.59 60 20 hour 1.51 1.13 0.57 60 21 hour 1.50 1.13 0.58 60 22 hour 1.50 1.13 0.58 60 23 hour 1.51 1.13 0.57 60 24 hour 1.50 1.12 0.58 0 Release 0.01 0.04 0.02 0 Hold 15 min 0.01 0.04 0.02 20 Increase to failure 0.70 0.36 0.09 40 1.07 0.67 0.27 60 1.57 1.17 0.60 80 2.07 1.75 1.00 100 2.49 2.19 1.34 110 2.89 2.63 1.69 120 3.25 3.10 2.12 130 3.56 3.57 2.56 163.2 Failure 6.97 10.22 13.60
TABLE-US-00010 TABLE A6 Load/Deflection Data for Eccentric Compressive Strength on SIEP - Panel 3 Mid Point Base Load Top Deflection Deflection Deflection (kN) Comment (mm) (mm) (mm) 0 0.00 0.00 0.00 15 Dead load 0.58 0.42 0.13 15 Hold 30 min 0.60 0.43 0.14 0 Release 0.21 0.20 0.05 0 Hold 15 min 0.20 0.20 0.05 15 Dead load 0.60 0.45 0.14 15 Hold 15 min 0.62 0.47 0.15 60 Design load 1.95 1.79 1.06 60 Leave 15 min 2.06 1.89 1.10 60 1 hour 2.11 1.97 1.17 60 2 hour 2.10 1.96 1.15 60 3 hour 2.34 2.22 1.46 60 4 hour 2.40 2.29 1.52 60 5 hour 2.42 2.32 1.55 60 6 hour 2.44 2.35 1.59 60 7 hour 2.45 2.36 1.59 60 8 hour 2.46 2.36 1.59 60 9 hour 2.45 2.36 1.58 60 10 hour 2.45 2.36 1.58 60 11 hour 2.46 2.37 1.60 60 12 hour 2.46 2.37 1.59 60 13 hour 2.47 2.39 1.61 60 14 hour 2.46 2.37 1.60 60 15 hour 2.46 2.38 1.60 60 16 hour 2.46 2.37 1.59 60 17 hour 2.45 2.37 1.59 60 18 hour 2.44 2.35 1.58 60 19 hour 2.43 2.35 1.57 60 20 hour 2.44 2.36 1.60 60 21 hour 2.49 2.41 1.65 60 22 hour 2.42 2.33 1.57 60 23 hour 2.44 2.35 1.58 60 24 hour 2.45 2.35 1.59 0 Release 1.52 1.29 0.78 0 Hold 15 min 1.51 1.28 0.78 20 Increase to failure 2.04 1.71 1.22 40 2.59 2.22 1.63 60 3.01 2.81 2.10 80 3.53 3.37 2.39 100 4.01 3.89 2.81 110 4.33 4.15 3.12 120 4.62 4.51 3.49 130 4.96 4.88 3.82 136.7 Failure 7.65 11.11 14.39
EXAMPLE 4
[0086] Double panels in accordance with the present invention were constructed consisting of two single SIEP wall panels. The single panel was of overall size 12002400 mm and comprised perimeter framing sections mitred and retained together with corner jointing brackets. The corner brackets were inserted into the perimeter profiles, through fixed, and spot welded.
[0087] A 1.2 m2.4 m by 9 mm thick magnesium silicate based board was fixed to each face of the single panel using 5.5 mm diameter65 mm long HILTI coated self-drilling wing tip screws. The board was fixed to the panel at nominally 300 mm centres to the perimeter framework. The fixings were placed 20 mm from the board edges. A panel core of polyurethane (PU) foam was injected into the cavity created by perimeter profiles and panel facing sheets and adhered to these components by its own adhesive properties whilst curing. Oriented strand board, Grade3 (OSB/3), 45 mm wide11 mm thick, were fitted into the perimeter frame profile, as perimeter infill, along the head and base of each single panel.
[0088] Each double panel assembly was connected together by means of an OSB/3 strip with nominal dimensions of 92 mm wide11 mm thick2400 mm long, such that the strip was fitted into the perimeter frame profile, as a jointing spline, along the vertical edges of the adjoining panels. The splines were bedded on joint sealant.
[0089] The panel was fixed into the test chamber such that the face of the panel would be subjected to the heat-rain and freeze thaw accelerated weathering test regime as follows:
Heat Rain80 Cycles
[0090] Heating to 70 C. rising over 1 hour and maintaining at 70 C.5 at 10-15% RH for a further 2 hours. [0091] Followed by spraying with water (water temp 15 C.) at 1 l/m2/min for 1 hour. [0092] Draining for 2 hours. [0093] On completion of the heat rain cycles the wall was conditioned for 48 hours at a temperature between 10 and 25 C. with a minimum RH of 50%.
Heat Cold5 Cycles
[0094] Exposure to 50 C.5 with a rise of 1 hour and maximum 10%RH for 7 hours. [0095] Exposure to 20 C.5 with a fall over 2 hours and hold for 14 hours. [0096] The test panel was inspected every 4 heat rain cycles and daily under the heat cold cycles to observe changes in the visual characteristics of the panel. [0097] On completion of the cyclic testing the wall was left to dry for 7 days.
Results
[0098] The wall was thoroughly examined for defects. No visible damage was noted to the face of the panel during the test regime or on completion of the test regime
EXAMPLE 5
[0099] Thermal Transmittence (U-value) of panels in accordance with the present invention according to BS EN ISO 6946.
EXAMPLE 6
[0100] Thermal transmittance measurements were made in the NPL Rotatable wall Guarded Hot Box, described in NPL Report CBTLM 25. Where relevant, the equipment and measurement procedures are in accordance with the requirements of BS EN ISO 8990. The main features of the equipment are: [0101] the interior dimensions of the hot box are 2.4 m2.4 m [0102] all surfaces seen by the test element are matt black [0103] there are 25 air temperature sensors, 75 mm from the holder panel face, positioned at the centres of squares of equal areas in front of the test element in both the hot and cold boxes [0104] the net heat flow direction is horizontal
Measurement Procedures
[0105] The measurement procedure used was essentially an air-to-air method. Thermocouples were also mounted on the hot and cold surfaces of the specimen to facilitate calculation of the environmental temperatures, as specified in BS EN ISO 8990.
[0106] The 2 m2 m0.149 m thick, Insulated Engineered Panel, was mounted in a 298 mm thick expanded polystyrene (EPS) surround panel. The heat flow through this surround panel was calculated from its thermal conductivity and the surface temperature difference across it. The thermal conductivity of the EPS material was measured in the NPL guarded hot plate facility.
[0107] The measurements were carried out with the test element installed verticallythat is with horizontal heat flow.
[0108] The small heat flow around the test element boundaries was calculated using the 2D FEA software tool THERM5 produced by the Lawrence Berkeley National Laboratory, USA. Thermal transmittance values quoted are the mean of five sets of readings taken at two-hourly intervals. Equilibrium is assumed when the maximum difference between the five thermal transmittance values is less than approximately 1.0%.
[0109] The standardised thermal transmittance value for R140 is given in Table 2, and a summary of the main experimental parameters is given in Table 3.
TABLE-US-00011 TABLE 5 Standardised Thermal Transmittance (U) Standardised thermal Environmental transmittance* temperature mean C. W/(m.sup.2K) SIP in accordance 11.86 0.44 with the present invention *Note: this U-value has been normalised to include the standard value of the total surface resistance of 0.17 (m.sup.2K)/W
TABLE-US-00012 TABLE 6 Measurement data Eco Mech Structurally Insulated Engineered Panel (///EMSIEP) Panel dimensions Height 2.002 m Width 2.003 m Thickness 0.149 m Measured values Mean warm air temperature 22.06 C. Mean warm baffle temperature 21.58 C. Mean cold air temperature 1.81 C. Mean cold baffle temperature 1.96 C. Power to hot box 41,666 W Air flow rate in the cold box 1.20 m/s Air flow rate in the hot box 0.25 m/s Calculated values Heat flux density through test element 9.089 W/m.sup.2 Warm side environmental temperature 21.89 C. Cold side environmental temperature 1.83 C. Environmental temperature difference 20.06 C. Environmental temperature mean 11.86 C. Measured thermal transmittance (U) 0.453 W/(m.sup.3 .Math. K) Total surface resistance 0.097 (m.sup.2 .Math. K)/W Standardised thermal transmittance.sup.[1] 0.439 W/(m.sup.2 .Math. K) Note .sup.[1]This U-value has been normalised to include the standard value of the total surface resistance of 0.17 (m.sup.2.K)/W
[0110] Offsite construction panels and systems, need to function on a number of levels (structural, thermal, moisture resistance, airtightness and whilst performing at their design optimum, undertake their core function of providing shelter).
[0111] Generally, increasing the structural performance will require additional internal structure within the panel, which decreases the thermal capacity of the panel and often results in an increase in thermal bridging.
[0112] An embodiment of the present invention has an integrated internal steel frame which increases the structural capacity of the system and provides its core airtightness. To negate thermal bridging issues of the steel frame, the frame may have a minimum thickness of high performance insulation bonded to both the external and internal faces of the steel frame, keeping it insulated against both heat and cold and therefore, negating thermal bridging across the wall panel.
[0113] The U Value of the panel can be adjusted for any climate or U Value requirementwith a minimum thickness of 180 mm it provides a U Value of 0.18 W/m2K (panel only) and can be designed and manufactured to provide a U Value below Passive House standards without the use of any additional add ons, tapes or mastic sealants simply by increasing the panel thicknessundertaken by varying the thickness of insulation within the panel without amending any other part of the panel or changing any other construction detail.
EXAMPLE 7
[0114] Double panels in accordance with the present invention were used consisting of two single SIEP wall panels. The single panel was of overall size 12002400 mm and comprised perimeter framing sections mitred and retained together with corner jointing brackets. The corner brackets were inserted into the perimeter profiles, through fixed, and spot welded. A 1.2 m2.4 m by 9 mm thick magnesium silicate based board was fixed to each face of the single panel using 5.5 mm diameter65 mm long Hilti coated self-drilling wing tip screws. The board was fixed to the panel at nominally 300 mm centres to the perimeter framework. The fixings were placed 20 mm from the board edges. A panel core of polyurethane (PU) foam was injected into the cavity created by perimeter profiles and panel facing sheets and adhered to these components by its own adhesive properties whilst curing. Oriented strand board, Grade3 (OSB/3), 45 mm wide11 mm thick, were fitted into the perimeter frame profile, as perimeter infill, along the head and base of each single panel.
[0115] Each double panel assembly was connected together by means of an OSB/3 strip with nominal dimensions of 92 mm wide11 mm thick2400 mm long, such that the strip was fitted into the perimeter frame profile, as a jointing spline, along the vertical edges of the adjoining panels. The splines were bedded on joint sealant.
Test Programme
[0116] Wind loading to CWCT.sup.1 standards on 2.42.4 m panel [0117] Soft and hard body impact on the SIEP panel in accordance with BS 8200.sup.2, as used in the wind load test above [0118] ETAG004.sup.3 accelerated weathering test (hygrothermal) on a 2.6 m tall by 3.2 m wide sample followed by wind loading and soft and hard body impact testing to BS8200
Uniformly Distributed Wind Loading
[0119] The full size panel was placed in a rigid steel frame such that it was simply supported on four sides. An air bag was positioned on the face of the panel and a reaction board was placed over this butting up-to and tied to the external steel test rig frame.
[0120] A series of linear displacement transducers were located on an independent scaffold frame reading onto the rear of the panel.
[0121] A load was applied to the panel via the air bags to 1.68 kPa. This was released and the system was allowed to recover. This was repeated twice before increasing the load to 2 kPa then 3 kPa. On releasing the load the samples were examined for any signs of damage before taking the panel to 15 kpa releasing the load and examining for any damage.
Soft and Hard Body Impact
[0122] This test was conducted on test panels which had already been subjected to Wind Load and ETAG004 Accelerated Weathering, therefore the sample preparation is as detailed above.
[0123] For the soft body impact tests a canvas bag containing 50 Kg of lead shot was suspended from a 3 m rope and allowed to swing at the face of the panel at an angle to give a maximum impact energy of 500 Nm.
[0124] Each panel was impacted at the position considered to be the weakest position i.e. at the centre of the panel. Any damage was noted.
[0125] For the hard body impact test each wall was laid down on the laboratory strong floor and a steel ball of 1 Kg mass and 62.5 mm diameter was released onto the face of the wall panel from a height of 1 m above the face of the panel providing an impact energy of 10 N-m. Any damage was noted.
ETAG004 Accelerated Weathering
[0126] The 2.4 m wide by 2.4 m high wall was fixed into a rigid steel frame which was fixed into the hygrothermal test chamber such that the face of the panel was exposed to the cyclic test conditions as follows:
Heat Rain80 Cycles
[0127] Heating to 70 C. rising over 1 hour and maintaining at 70 C.5 at 10-15% RH for a further 2 hrs. [0128] Followed by spraying with water (water temp 15 C.) at 1 l/m2/min for 1 hour. [0129] Draining for 2 hours. [0130] On completion of the heat rain cycles the wall was conditioned for 48 hours at a temperature between 10 and 25 C. with a minimum RH of 50%.
Heat Cold5 Cycles
[0131] Exposure to 50 C.5 with a rise of 1 hour and maximum 10%RH for 7 hours. [0132] Exposure to 20 C5 with a fall over 2 hours and hold for 14 hours. [0133] The test panel was inspected every 4 heat rain cycles and daily under the heat cold cycles to observe changes in the visual characteristics of the panel. [0134] On completion of the accelerated weathering test the panel was subjected to a wind loading test and soft and hard body impact testing as detailed in section 4.1 and 4.2 above.
Results
Uniformly Distributed Wind Loading
[0135] The maximum uniformly distributed wind load applied to the system was 17 kPa with no failure of the panel and no visible damage to the face of the panel. The test was stopped due to the limit of the test rig being reached.
[0136] A load deflection graph is given in
Soft and Hard Body Impact
[0137] The soft body impactor caused no damage to the system at an impact energy of 500 Nm.
[0138] The hard body impactor caused no damage to the system under an impact energy of 10 Nm.
ETAG004 Accelerated Weathering
[0139] The test panel showed no signs of deterioration under the accelerated weathering programme. There was no warping, blistering or cracking of the face of the panel After the accelerated weathering two bays of the panel were subjected to a negative wind load test and to a soft body impact test.
[0140] The panel achieved a maximum 15kpa negative wind load with no failure of the panel and no visible damage to the face of the panel. The test was stopped due to the limit of the test rig being reached.
[0141] A load deflection graph is given in
[0142] The panel showed no signs of damage under the soft body impact of 500 N-m or the hard body impact energy of 10 N-m.
Discussion
Uniformly Distributed Wind Loading
[0143] Under wind loading the performance as determined by the testing was related to the banded wind loads. Hence in the first instance a design loading of 2 kPa was applied and the deflection of the SIEP was not allowed to exceed span/200 or 12 mm deflection whichever was the lesser.
[0144] At 2 kPa the maximum recorded deflection on the system was 6.6 mm and the residual deflection was 0.9 mm. The maximum recorded deflection on the system tested after being subjected to the accelerated weathering test regime was 4.6 mm and the residual deflection was 1.6 mm.
[0145] Consequently under the design load and on unloading, the deflections were less than the limits set in the Standard.sup.1.
[0146] The standard wall was taken to 17 kPa before releasing the load and the wall subject to the accelerated weathering test regime was taken to 15 kPa. The panels were not taken to failure.
Soft and Hard Body Impact
[0147] The impact tests were carried out to BS 8200 which categorises zones that the system may be used in depending on the performance under both soft body and hard body impact testing.
[0148] The soft body impact caused no damage to the panel at an impact energy of 500 Nm. The hard body impact caused no reportable damage to the face of the panel at an impact energy of 10 N-m.
[0149] As defined in Tables 2-4 in BS 8200, the system in an as received condition and after being subject to the accelerated test regime can be classed as Category B which is readily accessible to public and others with little incentive to exercise care; chance of accidents occurring and of misuse. It can be used in zones below 1.5 m and can be used in pedestrian thoroughfares.
[0150] There are no test impact values given for Category A walls. In each case the type and severity of vandalism needs to be carefully assessed and appropriate impact values determined.
[0151] The panels in accordance with an embodiment of the present invention are able to withstand the wind loads as given in the CWCT standards with a good safety factor against failure in an as received condition and when subjected to an accelerated weathering test regime.
[0152] Under soft and hard body impact performance the panel is able to be used at below 1.5 m in areas readily accessible to the public.
[0153] The system showed no deterioration after simulated long term weathering incorporating hygrothermal and heat cold conditions and although there is no direct correlation given in the standards for equating the number of cycles of heat/rain and heat/cold conditions that the sample has gone through to an expected life it is reasonable to say that the full cycle would indicate that a product would typically be expected to have a lifecycle of between 25 and 60 years depending on the installation standard and the exposure conditions the panel would be subjected to over that lifetime.
REFERENCES
[0154] 1 Centre for Windows and Cladding: [0155] a) Standard for Walls with ventilated rainscreens [0156] b) Standard for Testing of ventilated rainscreens (draft for development) [0157] c) Test Methods for ventilated rainscreens (draft for development) [0158] d) Guide to Good Practice for Facades [0159] 2 European Organisation of Technical Approvals [0160] Guideline for European Technical Approval of Kits for External Wall Cladding ETAG034, February 2008 [0161] 3 British Standards Institution [0162] Code of Practice for the Design of Non-Loadbearing External Vertical Enclosures for Building BS 8200:1985 [0163] 4 European Organisation of Technical Approvals Guideline for European Technical [0164] Approval of External Thermal Insulation Composite Systems with Rendering ETAG004, 2000.
EXAMPLE 8
[0165] A panel in accordance with the present invention had overall dimensions of 2408 mm high by 2944 mm wide by 146 mm thick. The specimen was clad on each face with a layer of 9 mm thick magnesium silicate based board and comprised a profiled galvanized mild steel frame to G275 grade which sandwiched a 130 mm thick polyurethane core insulation referenced H1246-1 MD192140.
[0166] The test was conducted in accordance with Clause 8 of BS 476: Part 211:1987 Methods for determination of the fire resistance of loadbearing elements of construction.
[0167] The panel was judged on its ability to comply with the performance criteria for loadbearing capacity, integrity and insulation. The panel was mounted within a steel support frame such that both vertical edges had freedom of movement.
[0168] The perimeter frame was profiled galvanised mild steel to G275 grade, 1 mm thick; Cornoer jointing brackets were also profiled galvanised mild steel to G275 grade, 1 mm thick, fixed by spot welding; the panel core was a polyurethane foam (Elastogram), 45 kg/m.sup.3, 130 mm thick and injected into a cavity formed by the frame and the panel facing sheets; panel facings were magnesium silicate based board, 1050 kg/m.sup.3, 9 mm thick and screwed to the perimeter frame; joint sealant was a silicone sealant for jointing splines and perimeter frame profile where panels abut one another; jointing splines were orientated strand board, OSB, grade 2, 92 mm wide11 mm thick1220 mm long.
[0169] The furnace used was controlled so that its mean temperature complied with the requirements of BS 476: Part 20: 1987, clause 3.1.using six mineral insulated thermocouples distributed over a plane 100 mm from the surface of the test construction.
[0170] Thermocouples were provided to monitor the unexposed surface of the specimen and the output of all instrumentation was recorded at no less then 1 minute intervals.
[0171] A roving thermocouple was available to measure temperatures on the unexposed surface of the specimens at any position that might appear to be hotter than the temperatures indicated by the fixed thermocouples.
[0172] Cotton pads and gap gauges were available to evaluate the integrity of the panel. After the first 5 minutes of testing and for the remainder of the test, the furnace atmospheric pressure was controlled so that it complied with the requirements of BS 476: Part 20: 1987, clause 3.2.2. The calculated differential relative to the laboratory atmosphere at the top of the specimen was 18 (+/2) Pa.
Test Observations
[0173] All observations are from the unexposed face unless noted otherwise.
[0174] The ambient air temperature in the vicinity of the test construction was 12 oC at the start of the test with a maximum variation of +1 oC during the test. [0175] Time (mins) [0176] 00 00 The test commences. [0177] 04 30 Sight smoke release is evident at the head of the specimen. [0178] 20 00 The smoke release increases in volume from the head of the assembly. [0179] 28 00 Steam issues from the base of each vertical joint, which emit droplets of moisture, [0180] 30 00 The specimen continues to satisfy the load bearing, insulation and integrity criteria of the test. [0181] 42 00 Slight smoke release is evident coincident with thermocouple No. 10 along the right side vertical joint. [0182] 50 00 Slight smoke release is evident from the left side vertical joint coincident with thermocouple No. 9. [0183] 52 40 The maximum temperature rise is exceeded by thermocouple No. 3. Insulation failure is deemed to occur [0184] 60 00 The specimen continues to satisfy the load bearing and integrity criteria of the test. [0185] 70 00 The specimen continues to satisfy the load bearing and integrity criteria of the test.
TABLE-US-00013 TABLE 7 Mean surface temperature with the temperature/time relationship specified in the Standard Specified Actual Furnace Furnace Time Temperature Temperature Minutes Deg. C. Deg. C. 0 20 17 3 502 565 6 603 637 9 663 691 12 706 735 15 739 765 18 766 782 21 789 809 24 809 801 27 826 817 30 842 854 33 856 865 36 869 882 39 881 891 42 892 900 45 902 908 48 912 916 51 921 919 54 930 932 57 938 931 60 945 942 63 953 957 66 960 957 69 966 968 70 968 972
TABLE-US-00014 TABLE 8 Individual and Mean Temperatures Recorded on the Unexposed Surface of The Panel Mean Time T/C T/C T/C T/C T/C Temp Min- Number 2 Number 3 Number 4 Number 5 Number 6 Deg. utes Deg. C. Deg. C. Deg. C. Deg. C. Deg. C. C. 0 12 12 12 13 13 12 3 12 12 12 13 13 12 6 12 12 12 13 13 12 9 12 12 12 13 13 12 12 12 12 12 13 13 12 15 12 12 12 13 13 12 18 12 12 12 13 13 12 21 12 12 12 13 13 12 24 12 12 12 13 13 12 27 12 12 12 13 13 12 30 12 12 13 13 13 13 33 12 17 13 13 13 14 36 12 89 31 13 21 33 39 48 100 84 27 69 66 42 100 105 101 74 100 96 45 103 120 104 101 103 106 48 111 145 109 105 107 115 51 129 169 124 112 120 131 54 150 210 139 135 141 155 57 171 243 154 161 159 178 60 209 270 178 203 191 210 63 240 285 207 238 230 240 66 264 295 231 266 264 264 69 279 302 255 283 283 280 70 282 305 262 287 287 285
TABLE-US-00015 TABLE 9 Individual Temperature Recorded At Various Positions On The Unexposed Surface of The Panel T/C T/C T/C T/C T/C Number Number Number Number Number Time 7 8 9 10 11 Minutes Deg. C. Deg. C. Deg. C. Deg. C. Deg. C. 0 14 15 16 16 15 3 14 15 16 16 15 6 14 15 16 16 15 9 14 15 16 16 19 12 15 15 16 16 28 15 15 16 16 16 35 18 16 16 17 17 39 21 17 16 17 18 42 24 19 17 19 20 45 27 27 17 21 24 47 30 33 18 24 28 50 33 37 20 27 33 54 36 39 28 31 38 58 39 41 40 37 46 67 42 45 49 46 57 77 45 50 61 59 67 86 48 57 75 71 76 91 51 69 85 82 88 96 54 76 95 91 96 99 57 80 100 98 101 102 60 82 101 101 106 105 63 86 103 103 110 107 66 93 109 111 115 111 69 99 118 118 120 121 70 101 121 119 123 126
TABLE-US-00016 TABLE 10 Recorded Deflection of Specimen During the Test Deflec- Deflec- Time Deflection Deflection Deflection Deflection tion tion Min- Number Rate Number Rate Number Rate utes 1 mm 1 mm 2 mm 2 mm 3 mm 3 mm 0 0 0 0 0 0 0 3 0 0 3 0 4 0 6 1 0 3 0 5 0 9 1 0 4 0 5 0 12 2 0 6 1 5 0 15 4 1 9 1 12 4 18 6 1 13 1 18 2 21 7 0 16 1 22 2 24 7 0 18 1 26 1 27 9 1 21 1 27 0 30 12 1 27 2 25 1 33 15 1 35 3 21 1 36 18 1 40 0 20 0 39 17 0 40 0 20 0 42 16 0 40 0 20 0 45 16 0 40 0 20 0 48 17 0 40 0 20 0 51 20 1 41 0 20 1 54 23 1 41 0 19 0 57 24 0 41 0 19 0 60 24 0 40 1 19 0 63 22 1 40 0 19 0 66 20 1 40 0 19 0 69 19 0 40 0 19 0 70 19 0 40 0 19 0 Positive readings indicate movement towards the heating conditions
[0186]
[0187]
[0188] The load bearing capacity of the panel was satisfied for 70 minutes. Regarding integrity, there was no collapse of the panel, no sustained flaming on the unexposed surface and no loss of impermeability. These requirements were satisfied for 70 minutes.
[0189] Regarding insulation, the standard requires that the mean temperature rise of the unexposed surface shall not be greater than 140 C. and that the maximum temperature rise shall not be greater than 180 C. These requriements were satisfied for a period of 52 minutes after which time a temperature rise in excess of 180 C. was recorded on one thermocouple.
[0190] Referring to
[0191] At the corners of the rectangular frame are releasable securing means in the form of two screws 220 and complementarily shaped threaded bores 222 to enable the frame members to be secured to one another.
[0192] Also provided is an inlet 224 extending from the outer face of the frame to it's inner face which allows the passage of fluid during the manufacture of a panel and which can be selectively sealed. During manufacture containment boards can be positioned in place framed by the frame members and forming a space between containment boards. Expanding foam can then be injected through the inlet to the interior which is formed between the containment boards and the frame of the jig. The inlet can be sealed and the foam allowed to set. Once set the jig can be disassembled and the panel assembly is formed.